Section 2 — Post Installation Start-up and Adjustments

Air-cooled 11 kW Generators

DANGER

Proceed with caution! Generator power voltage is now supplied to the transfer switch. Contact with live transfer switch parts will result in dan- gerous and possibly fatal electrical shock.

10.Connect an accurate AC voltmeter and a fre- quency meter across transfer switch terminal lugs E1 and E2. Voltage should be 242-252 volts; frequency should read about 61-63 Hertz.

11.Connect the AC voltmeter test leads across ter- minal lug E1 and neutral; then across E2 and neutral. In both cases, voltage reading should be 121-126 volts AC.

12.Set the generator’s main circuit breaker to its OFF (or open) position. Let the engine run at no- load for a few minutes to stabilize internal engine generator temperatures.

13.Set the generator's AUTO/OFF/MANUAL switch to OFF. The engine should shut down.

NOTE:

It is important not to proceed until certain that generator AC voltage and frequency are correct and within the stated limits. Generally, if both AC frequency and voltage are high or low, the engine governor requires adjustment. If frequency is cor- rect, but voltage is high or low, the generator’s voltage regulator requires adjustment.

2.4GENERATOR TESTS UNDER LOAD

To test the generator set with electrical loads applied, proceed as follows:

1.Set generator’s main circuit breaker to its OFF (or open) position.

2.Turn OFF all loads connected to the transfer switch terminals T1 and T2.

3.Set the generator's AUTO/OFF/MANUAL switch to OFF.

4.Turn OFF the utility power supply to the transfer switch, using the means provided (such as a util- ity main line circuit breaker).

Do not attempt manual transfer switch opera- tion until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.

5.Manually set the transfer switch to the STANDBY position, e.g., load terminals connected to the generator's E1/E2 terminals. The transfer switch operating lever should be down.

6.Set the generator's AUTO/OFF/MANUAL switch to MANUAL. The engine should crank and start immediately.

7.Let the engine stabilize and warm up for a few minutes.

8.Set the generator’s main circuit breaker to its ON (or closed) position. Loads are now powered by the standby generator.

9.Turn ON electrical loads connected to transfer switch T1 and T2. Apply an electrical load equal to the full rated wattage/amperage capacity of the installed generator.

10.Connect an accurate AC voltmeter and a frequen- cy meter across terminal lugs E1 and E2. Voltage should be greater than 230 volts; frequency should be greater than 58 Hertz.

11.Let the generator run at full rated load for 20-30 minutes. Listen for unusual noises, vibration or other indications of abnormal operation. Check for oil leaks, evidence of overheating, etc.

12.When testing under load is complete, turn OFF electrical loads.

13.Set the generator's main circuit breaker to its OFF (or open) position.

14.Let the engine run at no-load for a few minutes.

15.Set the AUTO/OFF/MANUAL switch to OFF. The engine should shut down.

2.5CHECKING AUTOMATIC

OPERATION

To check the system for proper automatic operation, proceed as follows:

1.Set generator’s main circuit breaker to its OFF (or open) position.

2.Check that the AUTO/OFF/MANUAL switch is set to OFF.

3.Turn OFF the utility power supply to the transfer switch, using means provided (such as a utility main line circuit breaker).

4.Manually set the transfer switch to the UTILITY position, i.e., load terminals connected to the util- ity power source side.

5.Turn ON the utility power supply to the transfer switch, using the means provided (such as a util- ity main line circuit breaker).

6.Set the AUTO/OFF/MANUAL switch to AUTO. The system is now ready for automatic operation.

7.Turn OFF the utility power supply to the transfer switch.

With the AUTO/OFF/MANUAL switch at AUTO, the engine should crank and start when the utility source power is turned OFF. After starting, the transfer switch should connect load circuits to the standby side. Let the system go through its entire automatic sequence of operation.

10

Image 12
Contents Installation Introduction Authorized Dealer LocationTroubleshooting  Warning   Electrical Hazards  ‹ Standards IndexAccessory Features UNPACKING/INSPECTIONProtection Systems System SET LEDGenerator ‹ 1.4.2 120 Volt AC OutletSpecifications ‹ 1.6.1 Generator‹ 1.6.2 Engine Reconfiguring Fuel System Fuel Requirements RecommendationsFuel Consumption LocationBattery Installation Battery‹ 1.10.2 Transfer Switch Check Transfer Switch Operation Electrical ChecksBefore Initial START-UP Generator Tests Under Load Checking Automatic OperationVoltage Regulator Adjustment BREAK-IN Procedure‹ 3.2.1 Auto Position Automatic Transfer Operation Sequence of Automatic Operation‹ 3.2.2 OFF Position ‹ 3.2.3 Manual PositionSetting the Exercise Timer ‹ 3.6.1 LOW OIL Pressure Switch‹ 3.6.2 High Temperature Switch ‹ 3.6.3 Overcrank‹ 3.6.5 LOW Battery System FuseChecking the Engine OIL Level Changing the Engine OILChanging the Engine AIR Cleaner ‹ 4.3.2 OIL Change ProcedureChanging the OIL Filter Spark PlugsBattery Maintenance Adjusting GT-990 Valve ClearanceOUT of Service Procedure ‹ 4.12.1 Removal from ServiceCorrosion Protection Cooling System‹ 4.12.2 Return to Service Service Schedule Be performed by the nearest Authorized DealerTroubleshooting Guide Problem Cause CorrectionInstallation Diagram Control Panel BOX Customer Connection Charger Engine Alternator Exploded Views and Parts Lists Part NO. QTY Description Air-cooled 11 kW Generators Control Panel Drawing No E4879-D ASSEMBLY, Home Standby Exploded Views and Parts Lists QTY Description 102 Screw Hhtt M6-1.0 X 10 YC Alternator Air-cooled Pulleys Drawing KW Generators No E4880 FRAME, Mounting SS HSB Air-cooled 11 kW Generators Regulator Drawing No E4881-C CASTING, Twin Regulator Housing Air-cooled 11 kW Generators Air-cooled 11 kW Generators Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingGenerac Power SYSTEMS, INC

004916-0 specifications

Generac Power Systems 004916-0 is a robust and efficient solution for home and commercial power needs, designed to provide reliable electricity during outages and emergencies. This model is a standout generator, well-regarded for its technology and features that cater to users looking for both performance and dependability.

One of the main features of the 004916-0 is its powerful engine. It is equipped with a Generac G-Force engine, which is engineered for durability and high performance. This engine provides a reliable source of power, ensuring that homes and businesses can maintain essential functions during power interruptions. Its impressive starting capability and consistent performance make it a trusted choice for many users.

The generator also boasts an automatic transfer switch, which facilitates a smooth transition to generator power when the grid goes down. This feature minimizes disruption, as it ensures that critical systems like refrigeration, heating, and medical equipment remain operational without manual intervention. The transfer switch allows the generator to kick in within seconds of detecting a power loss, providing peace of mind for users.

In terms of technology, the 004916-0 incorporates advanced features such as Mobile Linkā„¢ remote monitoring. This innovative technology allows users to monitor the status of their generator from anywhere via a smartphone or tablet. Users can easily check power levels, receive maintenance alerts, and ensure that their system is running efficiently, providing enhanced control and convenience.

Another notable characteristic is its innovative enclosure design, which minimizes noise during operation. This makes the 004916-0 suitable for residential areas where noise pollution can be a concern. The generator's sound-dampening technology ensures that it operates quietly, providing a more pleasant environment for users and neighbors alike.

Additionally, the generator is built with user-friendly controls, allowing for easy start-up and operations. The intuitive interface simplifies monitoring and adjustments, making it accessible even for those who may not be technically inclined.

Generac Power Systems 004916-0 represents a blend of power, reliability, and advanced technology, making it a top choice for anyone seeking a dependable backup power solution. Its features are designed to meet the challenges of modern power outages, offering users the comfort and security they need in times of uncertainty. Whether for home or business use, the 004916-0 stands out as a reliable partner in power management.