Generac Power Systems 004916-0 owner manual Voltage Regulator Adjustment, BREAK-IN Procedure

Page 13

Section 3 — Operation

With the generator running and loads powered by generator AC output, turn ON the utility power supply to the transfer switch. The following should occur:

After about six seconds, the switch should transfer loads back to the utility power source.

About one minute after retransfer, the engine should shut down.

Air-cooled 11 kW Generators

4.Run the unit for one hour at 25% rated load.

5.Run the unit for one hour at 50% rated load.

6.Run the unit for one hour at 75% rated load.

7.Run the unit for one hour at 100% rated load.

8.Turn ON the utility power supply to the transfer switch, which will allow the transfer switch to transfer back to utility power. The unit will con- tinue to run for one minute and then shut down.

2.6VOLTAGE REGULATOR

ADJUSTMENT

With the frequency between 60-60.5 Hertz, slowly turn the slotted potentiometer (Figure 2.1) until line voltage reads 247-252 volts.

NOTE:

The access panel on top of the control panel must be removed to adjust the voltage regulator.

Figure 2.1 – Voltage Adjustment Potentiometer

NOTE:

The voltage regulator is housed inside the gen- erator's control panel. The regulator maintains a voltage in direct proportion to frequency at a 2-to-

1ratio. For example, at 62 Hertz, line-to-neutral voltage will be 124 volts.

3.1BREAK-IN PROCEDURE

Once the unit has been installed and all electrical checks have been made, it is strongly recommended that the following “Break-in Procedure” be completed to ensure correct generator operation in the future.

1.Set the generator’s AUTO/OFF/MANUAL switch to AUTO.

2.Turn OFF the utility power supply to the transfer switch using the means provided (such as a utility main line circuit breaker).

3.The unit will start, and the transfer switch will transfer to standby.

9.Allow the unit to cool.

10.Set the generator's AUTO/OFF/MANUAL switch to OFF. Remove the 7.5A and 15A fuses from the generator control panel. Disconnect the battery cables as outlined in “General Hazards” (page 2).

11.Drain the oil and remove the oil filter. Replace the oil filter according to Section 4.4, “Changing the Oil Filter”. Replace the oil with synthetic oil as recommended in Section 4.3, “Changing the Engine Oil”.

12.Reconnect the battery cables as outlined in “General Hazards” (page 2) and insert the 5A and 15A fuses into the generator control panel. The generator is now ready for service.

3.2USING THE AUTO/OFF/MANUAL SWITCH (FIGURE 3.1)

‹3.2.1 “AUTO” POSITION

Selecting this switch position activates fully automat- ic system operation. It also allows personnel to start and exercise the engine every seven days with the set- ting of the exercise timer (see Section 3.5).

Figure 3.1 – Generator Control Panel

11

Image 13
Contents Installation Authorized Dealer Location IntroductionTroubleshooting  Warning  ‹ Standards Index  Electrical Hazards UNPACKING/INSPECTION Accessory FeaturesProtection Systems System SET LED‹ 1.4.2 120 Volt AC Outlet Generator‹ 1.6.1 Generator Specifications‹ 1.6.2 Engine Fuel Requirements Recommendations Reconfiguring Fuel SystemFuel Consumption LocationBattery Battery Installation‹ 1.10.2 Transfer Switch Electrical Checks Check Transfer Switch OperationBefore Initial START-UP Checking Automatic Operation Generator Tests Under LoadBREAK-IN Procedure Voltage Regulator Adjustment‹ 3.2.1 Auto Position Sequence of Automatic Operation Automatic Transfer Operation‹ 3.2.2 OFF Position ‹ 3.2.3 Manual Position‹ 3.6.1 LOW OIL Pressure Switch Setting the Exercise Timer‹ 3.6.2 High Temperature Switch ‹ 3.6.3 OvercrankSystem Fuse ‹ 3.6.5 LOW BatteryChecking the Engine OIL Level Changing the Engine OIL‹ 4.3.2 OIL Change Procedure Changing the Engine AIR CleanerChanging the OIL Filter Spark PlugsAdjusting GT-990 Valve Clearance Battery Maintenance‹ 4.12.1 Removal from Service OUT of Service ProcedureCorrosion Protection Cooling System‹ 4.12.2 Return to Service Be performed by the nearest Authorized Dealer Service ScheduleProblem Cause Correction Troubleshooting GuideInstallation Diagram Control Panel BOX Customer Connection Charger Engine Alternator Exploded Views and Parts Lists Part NO. QTY Description Air-cooled 11 kW Generators Control Panel Drawing No E4879-D ASSEMBLY, Home Standby Exploded Views and Parts Lists QTY Description 102 Screw Hhtt M6-1.0 X 10 YC Alternator Air-cooled Pulleys Drawing KW Generators No E4880 FRAME, Mounting SS HSB Air-cooled 11 kW Generators Regulator Drawing No E4881-C CASTING, Twin Regulator Housing Air-cooled 11 kW Generators Air-cooled 11 kW Generators MANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyGenerac Power SYSTEMS, INC

004916-0 specifications

Generac Power Systems 004916-0 is a robust and efficient solution for home and commercial power needs, designed to provide reliable electricity during outages and emergencies. This model is a standout generator, well-regarded for its technology and features that cater to users looking for both performance and dependability.

One of the main features of the 004916-0 is its powerful engine. It is equipped with a Generac G-Force engine, which is engineered for durability and high performance. This engine provides a reliable source of power, ensuring that homes and businesses can maintain essential functions during power interruptions. Its impressive starting capability and consistent performance make it a trusted choice for many users.

The generator also boasts an automatic transfer switch, which facilitates a smooth transition to generator power when the grid goes down. This feature minimizes disruption, as it ensures that critical systems like refrigeration, heating, and medical equipment remain operational without manual intervention. The transfer switch allows the generator to kick in within seconds of detecting a power loss, providing peace of mind for users.

In terms of technology, the 004916-0 incorporates advanced features such as Mobile Link™ remote monitoring. This innovative technology allows users to monitor the status of their generator from anywhere via a smartphone or tablet. Users can easily check power levels, receive maintenance alerts, and ensure that their system is running efficiently, providing enhanced control and convenience.

Another notable characteristic is its innovative enclosure design, which minimizes noise during operation. This makes the 004916-0 suitable for residential areas where noise pollution can be a concern. The generator's sound-dampening technology ensures that it operates quietly, providing a more pleasant environment for users and neighbors alike.

Additionally, the generator is built with user-friendly controls, allowing for easy start-up and operations. The intuitive interface simplifies monitoring and adjustments, making it accessible even for those who may not be technically inclined.

Generac Power Systems 004916-0 represents a blend of power, reliability, and advanced technology, making it a top choice for anyone seeking a dependable backup power solution. Its features are designed to meet the challenges of modern power outages, offering users the comfort and security they need in times of uncertainty. Whether for home or business use, the 004916-0 stands out as a reliable partner in power management.