Section 4 — Maintenance

Air-cooled 11 kW Generators

Figure 4.5 – Setting the Spark Plug Gap

4.7BATTERY MAINTENANCE

The battery should be inspected per the “Service Schedule,” Section 4.13. The following procedure should be followed for inspection:

1.Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.

2.Check the battery fluid level of unsealed batteries and, if necessary, fill with Distilled Water Only. Do not use tap water in batteries.

3.Have the state of charge and condition checked. This should be done with an automotive-type bat- tery hydrometer.

DANGER

Do not dispose of the battery in a fire. The battery is capable of exploding.

Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical attention; and

Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) of water. The bicar- bonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.

Lead-acid batteries present a risk of fire because they generate hydrogen gas. The

following procedures are to be followed:

DO NOT SMOKE when near the battery;

DO NOT cause flame or spark in battery area; and

Discharge static electricity from body before touch- ing the battery by first touching a grounded metal surface.

Be sure the AUTO/OFF/MANUAL switch is set to the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.

Be sure the utility power supply is turned off and the 5A and 15A fuses are removed from the generator control panel, or sparking may occur at the battery posts as the cables are attached and cause an explosion.

A battery presents a risk of electrical shock

and high short circuit current. The following pre- cautions are to be observed when working on batteries:

Remove the 7.5A and 15A fuses from the genera- tor control panel.

Remove watches, rings or other metal objects;

Use tools with insulated handles;

Wear rubber gloves and boots;

Do not lay tools or metal parts on top of the battery; and

Disconnect charging source prior to connecting or disconnecting battery terminals.

Do not open or mutilate the battery. Released electrolyte has been known to be harmful to the skin and eyes, and to be toxic.

The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following procedures are to be observed:

Wear full eye protection and protective clothing;

Where electrolyte contacts the skin, wash it off immediately with water;

16

4.8ADJUSTING GT-990 VALVE

CLEARANCE

After the first six months of operation, adjust the valve clearance in the engine (Figure 4.6).

Important: If feeling uncomfortable about doing this procedure or the proper tools are not available, please contact the Authorized Dealer for service assistance. This is a very important step to insure longest life for the engine.

To adjust valve clearance:

Make sure the engine is at room temperature (between 60° and 80° F).

Make sure that the spark plug(s) are removed.

Remove the four screws attaching the valve cover with a #2 or #3 phillips screwdriver.

Make sure the piston is at Top Dead Center (TDC) of its compression stroke (both valves closed). To get the piston at TDC, remove the screen at the top of the intake scroll to gain access to the intake fan. Rotate the engine by hand by rotating the fan while watching the piston through the spark plug hole. The piston should move back and forth. The pis- ton is at TDC when it is as forward as it can go.

Image 18
Contents Installation Introduction Authorized Dealer LocationTroubleshooting  Warning   Electrical Hazards  ‹ Standards IndexProtection Systems Accessory FeaturesUNPACKING/INSPECTION System SET LEDGenerator ‹ 1.4.2 120 Volt AC OutletSpecifications ‹ 1.6.1 Generator‹ 1.6.2 Engine Fuel Consumption Reconfiguring Fuel SystemFuel Requirements Recommendations LocationBattery Installation Battery‹ 1.10.2 Transfer Switch Check Transfer Switch Operation Electrical ChecksBefore Initial START-UP Generator Tests Under Load Checking Automatic OperationVoltage Regulator Adjustment BREAK-IN Procedure‹ 3.2.1 Auto Position ‹ 3.2.2 OFF Position Automatic Transfer OperationSequence of Automatic Operation ‹ 3.2.3 Manual Position‹ 3.6.2 High Temperature Switch Setting the Exercise Timer‹ 3.6.1 LOW OIL Pressure Switch ‹ 3.6.3 OvercrankChecking the Engine OIL Level ‹ 3.6.5 LOW BatterySystem Fuse Changing the Engine OILChanging the OIL Filter Changing the Engine AIR Cleaner‹ 4.3.2 OIL Change Procedure Spark PlugsBattery Maintenance Adjusting GT-990 Valve ClearanceCorrosion Protection OUT of Service Procedure‹ 4.12.1 Removal from Service Cooling System‹ 4.12.2 Return to Service Service Schedule Be performed by the nearest Authorized DealerTroubleshooting Guide Problem Cause CorrectionInstallation Diagram Control Panel BOX Customer Connection Charger Engine Alternator Exploded Views and Parts Lists Part NO. QTY Description Air-cooled 11 kW Generators Control Panel Drawing No E4879-D ASSEMBLY, Home Standby Exploded Views and Parts Lists QTY Description 102 Screw Hhtt M6-1.0 X 10 YC Alternator Air-cooled Pulleys Drawing KW Generators No E4880 FRAME, Mounting SS HSB Air-cooled 11 kW Generators Regulator Drawing No E4881-C CASTING, Twin Regulator Housing Air-cooled 11 kW Generators Air-cooled 11 kW Generators Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingGenerac Power SYSTEMS, INC

004916-0 specifications

Generac Power Systems 004916-0 is a robust and efficient solution for home and commercial power needs, designed to provide reliable electricity during outages and emergencies. This model is a standout generator, well-regarded for its technology and features that cater to users looking for both performance and dependability.

One of the main features of the 004916-0 is its powerful engine. It is equipped with a Generac G-Force engine, which is engineered for durability and high performance. This engine provides a reliable source of power, ensuring that homes and businesses can maintain essential functions during power interruptions. Its impressive starting capability and consistent performance make it a trusted choice for many users.

The generator also boasts an automatic transfer switch, which facilitates a smooth transition to generator power when the grid goes down. This feature minimizes disruption, as it ensures that critical systems like refrigeration, heating, and medical equipment remain operational without manual intervention. The transfer switch allows the generator to kick in within seconds of detecting a power loss, providing peace of mind for users.

In terms of technology, the 004916-0 incorporates advanced features such as Mobile Linkā„¢ remote monitoring. This innovative technology allows users to monitor the status of their generator from anywhere via a smartphone or tablet. Users can easily check power levels, receive maintenance alerts, and ensure that their system is running efficiently, providing enhanced control and convenience.

Another notable characteristic is its innovative enclosure design, which minimizes noise during operation. This makes the 004916-0 suitable for residential areas where noise pollution can be a concern. The generator's sound-dampening technology ensures that it operates quietly, providing a more pleasant environment for users and neighbors alike.

Additionally, the generator is built with user-friendly controls, allowing for easy start-up and operations. The intuitive interface simplifies monitoring and adjustments, making it accessible even for those who may not be technically inclined.

Generac Power Systems 004916-0 represents a blend of power, reliability, and advanced technology, making it a top choice for anyone seeking a dependable backup power solution. Its features are designed to meet the challenges of modern power outages, offering users the comfort and security they need in times of uncertainty. Whether for home or business use, the 004916-0 stands out as a reliable partner in power management.