Section 3 — Operation

Air-cooled 11 kW Generators

‹3.2.2 “OFF” POSITION

This switch position shuts down the engine. This position also prevents automatic operation.

‹3.2.3 “MANUAL” POSITION

Set the switch to Manual to crank and start the engine. Transfer to standby power will not occur unless there is a utility failure.

With the switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting normally occurs when utility power source voltage drops below a pre- set level or during the normal exercise cycle. To prevent possible injury that might be caused by such sudden starts, always set the switch to OFF and remove the fuses before working on or around the generator or transfer switch. Then, place a “DO NOT OPERATE” tag on the generator panel and on the transfer switch.

3.3AUTOMATIC TRANSFER

OPERATION

To select automatic operation, do the following:

1.Make sure the transfer switch main contacts are set to their “Utility” position, i.e., loads connected to the utility power source (Figure 3.2).

2.Be sure that normal utility power source voltage is available to transfer switch terminal lugs N1 and N2.

3.Set the generator’s AUTO/OFF/MANUAL switch to AUTO.

4.Set the generator’s main circuit breaker to its ON (or closed) position.

With the preceding steps complete, the generator will start automatically when utility source voltage drops below a preset level. After the unit starts, loads are transferred to the standby power source. Refer to Section 3.4, “Sequence of Automatic Operation.”

3.4SEQUENCE OF AUTOMATIC

OPERATION

The generator’s control panel houses a control logic circuit board. This board constantly monitors util- ity power source voltage. Should that voltage drop below a preset level, circuit board action will signal the engine to crank and start. After the engine starts, the circuit board signals the transfer switch to acti- vate and connect load circuits to the standby power supply (load terminal lugs T1/T2 connect to terminal lugs E1/E2).

Upon restoration of utility source voltage above a preset level, generator circuit board action signals the transfer switch to transfer loads back to that power supply. After retransfer, the engine is signalled to shut down.

The actual sequence of operation is controlled by sensors and timers on a control logic circuit board, as follows:

A.Utility Voltage Dropout Sensor

This sensor monitors utility source voltage.

If utility source voltage drops below about 70 percent of the nominal supply voltage, the sensor energizes a 15-second timer.

Once the timer has expired, the engine will crank and start.

B.Engine Warm-up Time Delay

This mechanism lets the engine warm up for about 10 seconds before the load is transferred to the standby source.

C.Utility Voltage Pickup Sensor

This sensor monitors utility power supply volt- age. When that voltage is restored above 70 per- cent of the nominal source voltage, a retransfer time delay starts timing.

D.Retransfer Time Delay

This timer runs for about 15 seconds.

At end of a 15-second delay, circuit board action de-energizes transfer relay in the transfer switch.

Retransfer to utility power source then occurs.

E.Engine Cool-down Timer

• When the load is transferred back to utility power source, the engine cool-down timer starts tim- ing.

• The timer will run for about one minute, and the generator will then shut down.

12

Image 14
Contents Installation Introduction Authorized Dealer LocationTroubleshooting  Warning   Electrical Hazards  ‹ Standards IndexProtection Systems Accessory FeaturesUNPACKING/INSPECTION System SET LEDGenerator ‹ 1.4.2 120 Volt AC Outlet‹ 1.6.2 Engine Specifications‹ 1.6.1 Generator Fuel Consumption Reconfiguring Fuel SystemFuel Requirements Recommendations Location‹ 1.10.2 Transfer Switch Battery InstallationBattery Before Initial START-UP Check Transfer Switch OperationElectrical Checks Generator Tests Under Load Checking Automatic Operation‹ 3.2.1 Auto Position Voltage Regulator AdjustmentBREAK-IN Procedure ‹ 3.2.2 OFF Position Automatic Transfer OperationSequence of Automatic Operation ‹ 3.2.3 Manual Position‹ 3.6.2 High Temperature Switch Setting the Exercise Timer‹ 3.6.1 LOW OIL Pressure Switch ‹ 3.6.3 OvercrankChecking the Engine OIL Level ‹ 3.6.5 LOW BatterySystem Fuse Changing the Engine OILChanging the OIL Filter Changing the Engine AIR Cleaner‹ 4.3.2 OIL Change Procedure Spark PlugsBattery Maintenance Adjusting GT-990 Valve ClearanceCorrosion Protection OUT of Service Procedure‹ 4.12.1 Removal from Service Cooling System‹ 4.12.2 Return to Service Service Schedule Be performed by the nearest Authorized DealerTroubleshooting Guide Problem Cause CorrectionInstallation Diagram Control Panel BOX Customer Connection Charger Engine Alternator Exploded Views and Parts Lists Part NO. QTY Description Air-cooled 11 kW Generators Control Panel Drawing No E4879-D ASSEMBLY, Home Standby Exploded Views and Parts Lists QTY Description 102 Screw Hhtt M6-1.0 X 10 YC Alternator Air-cooled Pulleys Drawing KW Generators No E4880 FRAME, Mounting SS HSB Air-cooled 11 kW Generators Regulator Drawing No E4881-C CASTING, Twin Regulator Housing Air-cooled 11 kW Generators Air-cooled 11 kW Generators PURCHASER’S/OWNER’S Warranty Responsibilities Your Warranty Rights and ObligationsMANUFACTURER’S Emission Control System Warranty Coverage Emission Control System Warranty Emission Related Parts Include the FollowingGenerac Power SYSTEMS, INC

004916-0 specifications

Generac Power Systems 004916-0 is a robust and efficient solution for home and commercial power needs, designed to provide reliable electricity during outages and emergencies. This model is a standout generator, well-regarded for its technology and features that cater to users looking for both performance and dependability.

One of the main features of the 004916-0 is its powerful engine. It is equipped with a Generac G-Force engine, which is engineered for durability and high performance. This engine provides a reliable source of power, ensuring that homes and businesses can maintain essential functions during power interruptions. Its impressive starting capability and consistent performance make it a trusted choice for many users.

The generator also boasts an automatic transfer switch, which facilitates a smooth transition to generator power when the grid goes down. This feature minimizes disruption, as it ensures that critical systems like refrigeration, heating, and medical equipment remain operational without manual intervention. The transfer switch allows the generator to kick in within seconds of detecting a power loss, providing peace of mind for users.

In terms of technology, the 004916-0 incorporates advanced features such as Mobile Link™ remote monitoring. This innovative technology allows users to monitor the status of their generator from anywhere via a smartphone or tablet. Users can easily check power levels, receive maintenance alerts, and ensure that their system is running efficiently, providing enhanced control and convenience.

Another notable characteristic is its innovative enclosure design, which minimizes noise during operation. This makes the 004916-0 suitable for residential areas where noise pollution can be a concern. The generator's sound-dampening technology ensures that it operates quietly, providing a more pleasant environment for users and neighbors alike.

Additionally, the generator is built with user-friendly controls, allowing for easy start-up and operations. The intuitive interface simplifies monitoring and adjustments, making it accessible even for those who may not be technically inclined.

Generac Power Systems 004916-0 represents a blend of power, reliability, and advanced technology, making it a top choice for anyone seeking a dependable backup power solution. Its features are designed to meet the challenges of modern power outages, offering users the comfort and security they need in times of uncertainty. Whether for home or business use, the 004916-0 stands out as a reliable partner in power management.