Section 3 – Maintenance

3.1 CHECKING THE ENGINE OIL LEVEL

For oil capacities and requirements, see “Engine Oil Requirements”. Check the engine crankcase oil level at least every eight hours of operation, or before each use. To check the engine oil level, proceed as follows (see Figure 3.1):

1.Be sure the generator is as level as possible.

2.Remove the dipstick and wipe it dry with a clean, lint-free cloth.

3.Install and tighten the dipstick cap; then, remove it again. The oil level should be at the dipstick “Full” mark.

4.If necessary, remove the oil fill cap on the rocker cover and slowly add oil until it reaches the dip- stick “Full” mark. DO NOT FILL ABOVE THE “FULL” MARK.

Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing this could damage the engine.

5.Install and tighten the oil fill cap and the dipstick before operating the engine.

3.2 CHANGING THE ENGINE OIL AND/OR OIL FILTER

Change the engine oil after the first 25 hours of operation. Thereafter, change the oil every 100 operating hours. Change the oil more frequently if operating consistently under heavy load or at high ambient temperatures.

Recreational Vehicle Generator

Change the engine oil filter after the first 25 hours of operation, and every 100 operating hours there- after.

To change the oil and/or oil filter, proceed as fol- lows (see Figure 3.1):

1.Run the engine until it is thoroughly warmed up (at least five minutes) then shut OFF the engine.

2.Immediately after the engine shuts OFF, pull the oil drain cover free of the base. Remove the plug from the tube with a 5/16” allen wrench and drain the oil into a suitable container. Loosening the oil fill cap will allow the crankcase to drain faster.

3.After the oil has drained, replace the plug onto the end of the oil drain tube. Retain the cover in the base.

4.With the oil drained, remove the old oil filter by turning it counterclockwise. Place a towel under- neath to catch excess oil.

5.Apply a light coating of clean engine oil to the gas- ket of the new filter. Fill the filter until saturated with clean oil.

6.Screw the new filter on by hand until its gasket lightly contacts the oil filter adapter. Then, tighten the filter an additional 3/4 to one turn.

7.Remove the dipstick and wipe it dry with a clean, lint-free cloth. This will be used later to check the oil level.

8.Remove the oil fill cap on the oil fill tube and slowly add the proper type and amount of rec- ommended oil (see “Engine Oil Requirements”). Periodically use the dipstick to check the oil level and continue to fill the crankcase until the oil reaches the dipstick “Full” mark. DO NOT FILL ABOVE THE “FULL” MARK.

9.Install and tighten the oil fill cap and the dipstick before operating the engine.

10.Start the engine and check for leaks.

Figure 3.1 – Oil Maintenance Features

G

GENERAC

E N

OHVIPOWERED

r , W

I

E R A C

P o w e r S y s t e m s , I n c .- W h it e

w a t e

 

 

 

 

 

 

 

 

 

GENERAC OHVI INDUSTRIAL ENGINE

QUIETPACT 40G

RV SERVICE LOCATOR: 1.800.333.1322

Oil Dipstick/Oil Fill

 

 

CONTROL CENTER

 

 

 

S T A R T

F U E L

C . B .

 

 

3 0 A

 

 

S T O P

P R I M E

 

 

 

 

F U S E

 

 

 

 

7.5 A

 

 

 

S E R V IC E A C C E S S P A N E L

 

 

AIR FILTER LOCATED BEHIND PANEL.

 

 

 

MAINTENANCE SCHEDULE

 

 

 

OIL LEVEL:

CHECK DAILY

 

 

 

AIR FILTER:

CLEAN PREFILTER

 

 

 

EVERY 100 HOURS. *

 

 

 

REPLACE ELEMENT

 

 

 

EVERY 250 HOURS. *

 

 

OIL & OIL FILTER:

CHANGE EVERY 100

 

 

 

HOURS. (OR ANNUALLY) *

 

 

 

*

 

 

 

SPARK PLUGS:

INSPECT & CLEAN

 

 

 

PLUGS EVERY 100

 

 

 

HOURS. REPLACE PLUGS

 

 

 

EVERY 500 HOURS.

 

 

 

(IF NECESSARY)

 

 

 

FUEL FILTER:

CHANGE EVERY 400

 

 

 

HOURS. (OR ANNUALLY)

To

Re

REPLACEMENT INFORMATION

 

 

PREFILTER P/N:

 

0D4511

 

m

AIR FILTER P/N:

 

0D3262

 

o

OIL FILTER P/N:

 

070185

 

SPARK PLUG P/N:

 

072347

 

v

FUEL FILTER P/N:

 

0D7515

 

e

OIL CAPACITY WITH FILTER:

0.8L/0.84QT

 

 

TEMPERATURE

SAE VISCOSITY

 

 

32˚F AND HIGHER

 

30

 

 

10˚F TO 100˚F

 

15W-40

 

 

0˚F TO 80˚F

 

10W-30

 

 

-20˚F TO 50˚F

 

5W-30

 

 

WHEN SERVICE OR PARTS ARE NEEDED IN

 

 

 

THE USA OR CANADA, CONTACT THE GENERAC

 

 

 

SERVICE LOCATOR AT 1-800-333-1322.

 

Oil Drain

Oil Filter

11

Image 13
Contents Air-cooled Recreational Vehicle Generators Introduction Authorized Service Dealer LocationPart Part II Installation Instructions Warning   Fire Hazards  Model Number Serial Number KW Rating Rated Voltage Generator IdentificationSpecifications SafetyGenerator Applicability ‹ 1.5.1 Fuel RequirementsFuel Consumption ‹ 1.5.5 GeneratorEngine OIL Requirements ‹ 1.5.6 Emissions Compliance PeriodAutomatic Choke Generator Control PanelBefore Starting the Engine ‹ 2.4.2 Engine Lubrication Starting the Generator‹ 2.4.3 Fuel Supply ‹ 2.4.4 Cooling and Ventilating AIRApplying Loads to Generator Stopping the GeneratorDo not Overload the Generator Protection Systems ‹ 2.9.3 Field Boost Additional Information‹ 2.9.4 Overvoltage Protection ‹ 2.10.2 Operation in High Grass or BrushChanging the Engine OIL AND/OR OIL Filter Checking the Engine OIL LevelClean AIR Intake Maintaining the Engine AIR Cleaner‹ 3.3.1 Cleaning the Foam Precleaner Cleaning the Generator Clean Spark ArrestorFuel Filter OUT of Service Procedure Battery Maintenance‹ 3.12.1 Removal from Service Exercising the GeneratorRV Generator Service Interval Adjusting Valve Clearance‹ 3.12.2 Return to Service Recreational Vehicle Generator Part  General Hazards   Fire Hazards  Equipment Description Purpose and Scope ManualStandards Booklets Major Features and Dimensions Drawing No D8716-J ‹ 2.1.1 Generator Location Location and Support‹ 2.1.2 Generator Support ‹ 2.1.4 Generator Restraint Generator Compartments‹ 2.2.2 Compartment Construction ‹ 2.2.1 Compartment Size‹ 2.2.3 Sound Insulating Materials ‹ 2.2.4 Acoustics‹ 2.3.1 Generator Airflow ‹ 2.2.5 Compartment Floor CutoutsCompartment Floor Cutout Drawing 0G3723-A Gasoline Fuel System ‹ 2.3.2 Testing the Installation‹ 2.4.1 Fuel Tank ‹ 2.4.2 Generator Fuel Supply LineFlexible Fuel Line Exhaust System‹ 2.5.1 Spark Arrestor Electrical Connections ‹ 2.5.2 Exhaust System Safety‹ 2.6.6 Power Supply Cord ‹ 2.6.5 Isolating Different Power Sources‹ 2.6.4 Conduit ‹ 2.7.1 Recommended Battery Battery Installation‹ 2.7.2 Battery Cables ‹ 2.7.3 Battery Cable Connections Optional Accessories‹ 2.7.4 Battery Compartment ‹ 2.8.1 Remote START/STOP PanelTesting Under Load Post Installation TestsBefore Initial START-UP Initial StartInstallation Checklist Problem Cause Correction Troubleshooting GuideElectrical Data Supplied by Customer Recreational Vehicle Generator Enclosure Drawing No D8352-K Part NO. QTY Description Recreational Vehicle Generator Generator Drawing No D8353-L QTY Description Exploded Views and Parts Lists QTY Exploded Views and Parts Lists GUARD, FAN Exploded Views and Parts Lists Long Block Assembly MANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyWarranty Schedule CONSUMER/PERSONAL Applications

004709-0 specifications

Generac Power Systems has established itself as a leader in the home backup generator market with its innovative products, and the Generac 004709-0 is no exception. Designed for homeowners seeking reliable power solutions during outages, this generator ensures peace of mind and uninterrupted operation for essential appliances and electronics.

One of the primary features of the Generac 004709-0 is its robust power output. With a powerful 7,500 running watts and a surge capacity of 9,000 watts, it can efficiently handle large loads, including central air conditioning units, refrigerators, and heat pumps. This generator operates on gasoline, providing an accessible fuel source readily available at most retail locations.

Equipped with a durable 420cc engine, the 004709-0 combines efficiency with exceptional performance. It features a low-oil shutdown system, which safeguards the engine from damage by automatically shutting off when oil levels become critically low. This feature ensures longevity and reliability, making it a dependable choice for homeowners.

The portability of the Generac 004709-0 is another notable characteristic. Weighing approximately 130 pounds, it comes with a built-in handle and sturdy wheels for easy transportation. This feature allows users to move the generator effortlessly from storage to the desired location, which is especially convenient during an emergency.

In addition to power and portability, the Generac 004709-0 boasts user-friendly controls. The control panel includes four 120V household outlets, a 12V automotive outlet, and a circuit breaker, offering flexibility for various connections. Furthermore, the generator is equipped with an easy-to-read fuel gauge and a low-fuel warning light, enhancing operational visibility.

Safety is also paramount in the design of this generator. It includes a powerful muffler that significantly reduces noise and meets stringent regulations for operation in residential areas. Additionally, the 004709-0 incorporates advanced technologies like the PowerDial which allows users to select the correct power level needed for various tasks easily.

Overall, the Generac Power Systems 004709-0 stands out due to its powerful output, user-friendly design, and safety features. Homeowners can rely on this generator to keep their homes powered during outages, ensuring comfort and security for themselves and their families. With its combination of innovation and practicality, the 004709-0 continues to exemplify Generac's commitment to quality and excellence in power solutions.