Generac Power Systems 04758-2, 04759-2, 04760-2 owner manual Checking The Engine Oil Level, Fuse

Page 19
Figure 3.3 – Low Oil Pressure and

Section 4 — Maintenance

Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators

Figure 3.3 – Low Oil Pressure and

High Temperature Switches

Low Oil Switch

 

High Temp Switch

 

 

 

 

 

 

The generator panel’s 5 amp fuse protects the battery charge circuit against overload. If the fuse element has melted open, battery charging capability will not be pos- sible. Replace the fuse using only an identical 5 amp replacement. To remove fuse, push cap down and rotate counterclockwise.

Figure 4.1 – Generator Control Panel

Figure 4.1 – Generator Control Panel Loosen

Oil‹ 3.7.3 OVERCRANK

Drain

Hose

Oil Filter

‹ 3.7.3 OVERCRANK

FUSE

5A

AUTO OFF MAN.

FUSE

15ASET EXERCISE

TIME

L o c a t e y o u r n e a r e s t 4.2CHECKING THE ENGINEFigure 4.2 — Oil Dipstick and Fill, 7 kW3.7.3.1 Approximate Crank Cycle Times d e a le r a t :

‹3.7.4 OVERSPEEDPOWER SYSTEMS, INC.

SYSTEM SET

LOW OIL

HIGH TEMP.

OVER SPEED

OVER CRANK

F L A S H IN G G R E E N L E D =

N O U T IL IT Y S E N S E 4 F L A S H IN G R E D L E D S =

E X E R C IS E R N O T S E T

This feature prevents the generator from damaging itself when it continually attempts to start and anoth- er problem, such as no fuel supply, prevents it from starting. The unit will crank and rest for a preset time limit. Then, it will stop cranking, and the LED will light indicating an overcrank failure. The AUTO/OFF/MANUAL switch will need to be set to OFF and then back to AUTO to reset the generator control board.

NOTE:

If the fault is not repaired, the overcrank feature will continue to activate.

4.2CHECKING THE ENGINE

OIL LEVEL

For oil capacities, see “Specifications,” Section 1.5. For engine oil recommendations, see Section 4.3.1. To check the engine oil level, proceed as follows (Figure 4.2):

1.Start the generator by moving the Auto/ Off/Manual switch to the MANUAL position. Allow it to run for a short while and then shut it down by moving the switch to the OFF position.

Figure 4.2 — Oil Dipstick and Fill, 7 kW

3.7.3.1 Approximate Crank Cycle Times

15 seconds ON

7 seconds OFF

7 seconds ON

7 seconds OFF

Repeat for 45 seconds Approximately 90 seconds total

‹3.7.4 OVERSPEED

This feature protects the generator from damage by shutting it down if it happens to run faster than the preset limit. This protection also prevents the gener- ator from supplying an output that could potentially damage appliances connected to the generator cir- cuit. Contact the nearest Generac Authorized Dealer if this failure occurs.

4.1FUSE

The generator panel’s 15 amp fuse (Figure 4.1) protects the DC control circuit against overload. The fuse is wired in series with the battery output lead to the panel. If the fuse element has melted open, the engine cannot crank or start. Replace the fuse using only an identical 15-amp replacement.

4.1FUSE Oil Dipstick and Fill

2.Remove the dipstick and wipe it dry with a clean cloth.

3.Install the dipstick; then, remove it again. The oil level should be at the dipstick “Full” mark. If nec- essary, add oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL” MARK.

Never operate the engine with the oil level

!below the “Add” mark on the dipstick. Doing this could damage the engine.

Generac® Power Systems, Inc. 17

Image 19
Contents Installation and Owner’s Manual Models 04758-2 6 kW NG, 7 kW LP 04759-2 12 kW NG, 12 kW LP04760-2 13 kW NG, 15 kW LP This manual should remain with the unitINTRODUCTION ‹ CONTENTS‹ OPERATION AND MAINTENANCE ‹ HOW TO OBTAIN SERVICEIntroduction during operation. Exercise care near running generators GENERAL HAZARDSDespite the safe design of this generator Parts of the generator are rotating and/or hot‹ STANDARDS INDEX ELECTRICAL HAZARDSFIRE HAZARDS EXPLOSION HAZARDSDANGER 1.1 UNPACKING/INSPECTION1.2 PROTECTION SYSTEMS 1.3 SYSTEM SET LEDFigure 1.1 - 7 kW, Single Cylinder GH-410 Engine 1.4 THE GENERATORFigure 1.2 - 12 kW/15 kW, V-twin GT-990/760 Engine ‹ 1.5.1 GENERATOR 1.5 SPECIFICATIONS‹ 1.5.2 ENGINE DANGER 1.8 RECONFIGURING THE FUEL SYSTEM1.6 FUEL REQUIREMENTS AND RECOMMENDATIONS 1.7 FUEL CONSUMPTIONFigure 1.4 - Demand Regulator 1.9 LOCATION1.8.2 12KW AND 15KW, 990CC ENGINES 1.9.1 GENERATORFigure 1.5 - Battery Cable Connections 1.10 BATTERY INSTALLATION1.11 THE BATTERY 1.9.2 TRANSFER SWITCH 1.9.2.1 7 kW, 12 kW and 15 kW Units2.1 BEFORE INITIAL START-UP 2.2 CHECK TRANSFER SWITCH OPERATION2.3 ELECTRICAL CHECKS 2.5 CHECKING AUTOMATIC OPERATION 2.4 GENERATOR TESTS UNDER LOADFigure 2.2 - Placement of Regulator 2.6 ADJUSTING THE REGULATOR NATURAL GAS ONLYFigure 2.1 - Dual Fuel Regulators Figure 2.5 - V-twin Full Load Speed Adjust Screw 2.7 ENGINE GOVERNOR ADJUSTMENTFigure 2.4 - V-twin Engine Governor Adjustment Figure 2.3 - Single Cylinder Engine Governor AdjustmentFigure 2.6 - Voltage Adjustment Potentiometer 2.8 VOLTAGE REGULATOR ADJUSTMENT3.1 BREAK-IN PROCEDURE 3.2 USING THE AUTO/OFF/MANUAL SWITCH FIGURE‹ 3.5.1 TRANSFER TO GENERATOR POWER SOURCE 3.3 AUTOMATIC TRANSFER OPERATION3.5 MANUAL TRANSFER OPERATION 3.4 SEQUENCE OF AUTOMATIC OPERATIONFigure 3.2 - Manual Transfer Switch Operation ‹ 3.5.2 TRANSFER BACK TO UTILITY POWER SOURCE‹ 3.7.1 LOW OIL PRESSURE SWITCH ‹ 3.7.2 HIGH TEMPERATURE SWITCH‹ 3.7.3 OVERCRANK Figure 3.3 - Low Oil Pressure and High Temperature Switches4.2 CHECKING THE ENGINE OIL LEVEL 4.1 FUSE4.4 CHANGING THE OIL FILTER 4.5 CHANGING THE ENGINE AIR CLEANER‹ 4.3.2 OIL CHANGE PROCEDURE 4.3 CHANGING THE ENGINE OILFigure 4.8 - Setting the Spark Plug Gap 4.7 BATTERY MAINTENANCEFigure 4.6 - 7 kW, Engine Air Cleaner Location Figure 4.7 - 12 kW and 15 kW Engine Air CleanerFigure 4.10 - Valve Clearance Adjustment 4.8 ADJUSTING VALVE CLEARANCE4.9 COOLING SYSTEM 4.10 ATTENTION AFTER SUBMERSION 4.12 OUT OF SERVICE PROCEDURE‹ 4.12.2 RETURN TO SERVICE ‹ 4.12.1 REMOVAL FROM SERVICE4.13 SERVICE SCHEDULE CORRECTION 5.1 TROUBLESHOOTING GUIDEPROBLEM CAUSEENGINE WIRING 24 Generac Power Systems, IncSection 6 - Electrical Data CUSTOMER CONTROL PANEL BOXCONNECTION 26 Generac Power Systems, Inc Electrical Schematic - 12 & 15 kW - Drawing No. 0D8501-BSection 6 - Electrical Data Section 6 - Electrical Data 28 Generac Power Systems, IncCUSTOMER 225A 30 Generac Power Systems, Inc224A Electrical Schematic - 7 kW - Drawing No. 0D9014-C 32 Generac Power Systems, Inc Section 7 - Exploded Views and Parts ListsPART NO. QTY. DESCRIPTION 34 Generac Power Systems, Inc PART NO. QTY. DESCRIPTION 27, 28 36 Generac Power Systems, Inc35, 36, 40 DESCRIPTION PART NO. QTY38 Generac Power Systems, Inc DESCRIPTION 14 20 40 Generac Power Systems, Inc1.25 FT 1.8 FT42 Generac Power Systems, Inc 3 FT 2.6 FT1.33 FT 44 Generac Power Systems, Inc DESCRIPTION 46 Generac Power Systems, Inc DESCRIPTION 48 Generac Power Systems, Inc DESCRIPTION Guardian Air-cooled 7 kW, 12 Drawing No. 0D3739-B 50 Generac Power Systems, IncALL DIMENSIONS IN MILLIMETERS INCHES Section 8 - MountingSection 9 - Notes CALIFORNIA AND FEDERAL EMISSION CONTROL WARRANTY STATEMENT YOUR WARRANTY RIGHTS AND OBLIGATIONSMANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIESEMISSION RELATED PARTS INCLUDE THE FOLLOWING EMISSION CONTROL SYSTEM WARRANTYTHIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING GENERAC POWER SYSTEMS TWO YEAR LIMITED WARRANTY FOR GUARDIANPREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS WARRANTY SCHEDULE