Section 3 — Post Installation Start-up and Adjustments

Air-cooled 15 kW Generators

3.Check utility power source voltage across termi- nals N1 and the transfer switch neutral lug; then across terminal N2 and neutral. Nominal line-to- neutral voltage should be 120 volts AC.

3.4GENERATOR TESTS UNDER LOAD

4.When certain that utility supply voltage is compat- ible with transfer switch and load circuit ratings, turn OFF the utility power supply to the transfer switch.

5.Set the generator's main circuit breaker to its OFF (or OPEN) position. Initial tests will be con- ducted at no-load condition.

6.On the generator panel, set the AUTO/OFF/ MANUAL switch to MANUAL. The engine should crank and start.

7.Let the engine warm up for about five minutes to allow internal temperatures to stabilize. Then, set the generator’s main circuit breaker to its ON (or closed) position.

DANGER

Proceed with caution! Generator power voltage is now supplied to the transfer switch. Contact with live transfer switch parts will result in dan- gerous and possibly fatal electrical shock.

8.Connect an accurate AC voltmeter and a fre- quency meter across transfer switch terminal lugs E1 and E2. Voltage should be 242-252 volts; frequency should read about 61-63 Hertz.

9.Connect the AC voltmeter test leads across ter- minal lug E1 and neutral; then across E2 and neutral. In both cases, voltage reading should be 121-126 volts AC.

10.Set the generator’s main circuit breaker to its OFF (or open) position. Let the engine run at no- load for a few minutes to stabilize internal engine generator temperatures.

11.Set the generator's AUTO/OFF/MANUAL switch to OFF. The engine should shut down.

NOTE:

It is important not to proceed until certain that generator AC voltage and frequency are correct and within the stated limits. Generally, if both AC frequency and voltage are high or low, the engine governor requires adjustment. If frequency is cor- rect, but voltage is high or low, the generator’s voltage regulator requires adjustment.

Do not attempt manual transfer switch opera- tion until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.

To test the generator set with electrical loads applied, proceed as follows:

1.Set generator’s main circuit breaker to its OFF (or OPEN) position.

2.Set the generator's AUTO/OFF/MANUAL switch to OFF.

3.Turn OFF the utility power supply to the transfer switch, using the means provided (such as a util- ity main line circuit breaker).

4.Manually set the transfer switch to the STANDBY position, i.e., load terminals connected to the generator's E1/E2 terminals. The transfer switch operating lever should be down.

5.Set the generator's AUTO/OFF/MANUAL switch to MANUAL. The engine should crank and start immediately.

6.Let the engine stabilize and warm up for a few minutes.

7.Set the generator’s main circuit breaker to its ON (or closed) position. Loads are now powered by the standby generator.

8.Turn ON electrical loads. Apply an electrical load equal to the full rated wattage/amperage capacity of the installed generator.

9.Connect an accurate AC voltmeter and a frequen- cy meter across terminal lugs E1 and E2. Voltage should be greater than 230 volts; frequency should be greater than 58 Hertz.

10.Let the generator run at full rated load for 20-30 minutes. Listen for unusual noises, vibration or other indications of abnormal operation. Check for oil leaks, evidence of overheating, etc.

11.When testing under load is complete, turn OFF electrical loads.

12.Set the generator's main circuit breakers to their OFF (or open) positions.

13.Let the engine run at no-load for a few minutes.

14.Set the AUTO/OFF/MANUAL switch to OFF. The engine should shut down.

11

Image 13
Contents Installation Authorized Dealer Location IntroductionSection Troubleshooting  Warning  ‹ Standards Index  Electrical Hazards Protection Systems UNPACKING/INSPECTIONSystem SET LED Generator Automatic Transfer SwitchReconfiguring Fuel System SpecificationsFuel Requirements Recommendations Fuel Consumption‹ 2.1.1 Remote Monitoring Connections Installation‹ 2.1.2 Roof Open Alarm ‹ 2.1.3 Transfer Switch ConnectionBattery Installation Before Initial START-UP Check Transfer Switch Operation BatteryElectrical Checks Generator Tests Under Load Checking Automatic Operation Adjusting the Regulator Natural GAS onlyEngine Governor Adjustment Voltage Regulator AdjustmentAutomatic Transfer Operation Sequence of Automatic Operation‹ 4.1.1 Auto Position ‹ 4.1.3 Manual Position‹ 4.4.1 Close to Normal Source Side Manual Operation‹ 4.4.2 Close to Emergency Source Side Voltage Checks‹ 4.4.3 Return to Normal Source Side ‹ 4.8.1 LOW OIL Pressure Switch Setting the Exercise Timer‹ 4.8.2 High Temperature Switch ‹ 4.8.3 OvercrankChecking the Engine OIL Level Changing the Engine OIL‹ 4.8.4 Overspeed ‹ 5.3.1 Engine OIL RecommendationsChanging the OIL Filter Changing the Engine AIR CleanerSpark Plugs Adjusting Valve Clearance Battery Maintenance‹ 5.12.1 Removal from Service OUT of Service ProcedureCooling System Corrosion Protection‹ 5.12.2 Return to Service ‹ 7 KW 40 KW Small Standby Generator Sets Service Maintenance Interval InformationMaintenance Level Level5 Tasks Maintenance Level Problem Cause Correction Troubleshooting GuideMounting Dimensions Electrical Data Control Panel BOX Transfer Switch 1VA GTS Exploded Views and Parts Lists Part NO. QTY. Description Air-cooled 15 kW Generators Control Panel Drawing No F5846 Description Exploded Views and Parts Lists Item Part NO. QTY. Description Exploded Views and Parts Lists Part NO. QTY Description Exploded QTY Description 7KW CASTING, Twin Regulator Housing Exploded Views and Parts Lists LUG Sldlss 250-#6 AL/CU MANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyGenerac Power Systems Standard Limited Warranty for

05176-0 specifications

Generac Power Systems 05176-0 is a powerful home standby generator designed to provide reliable backup power during outages. Known for its innovative technology and robust features, the 05176-0 model is part of Generac's Guardian Series, which is renowned for its reliability and ease of use.

One of the standout features of the Generac 05176-0 is its Generac G-Force engine, which is designed specifically for generator use. This automotive-grade engine is built to handle the rigors of prolonged operation, ensuring that homeowners have a dependable source of power. With a power output of 22 kW, it can handle the essential electrical loads of many homes, allowing users to power their lights, appliances, HVAC systems, and other necessary devices without interruption.

The 05176-0 comes equipped with a state-of-the-art transfer switch that automatically detects outages and begins the power restoration process within seconds. This automatic transfer switch eliminates the need for manual intervention, giving homeowners peace of mind that their power supply will seamlessly transition during a grid failure.

In terms of fuel efficiency, the Generac 05176-0 operates on either natural gas or liquid propane, providing flexibility for installation and operation. Its dual-fuel capability allows users to choose the fuel source that is most convenient and cost-effective for them.

Another notable feature is the generator’s Quiet-Test technology, which runs the generator at reduced RPMs for a self-test every week. This helps to ensure that the generator is operational and ready when needed while minimizing noise pollution in residential areas.

The model also boasts an intuitive LCD display that provides real-time information on the generator's status, including maintenance intervals and diagnostic information. This user-friendly interface simplifies monitoring and helps ensure that users can maintain optimal performance.

Moreover, the construction and design of the 05176-0 are intended for durability and weather resistance. With a robust enclosure made from high-quality materials, it is built to withstand harsh weather conditions, allowing homeowners to trust that their generator will perform reliably in any situation.

Overall, the Generac Power Systems 05176-0 stands out as a premium choice for homeowners seeking a reliable, efficient, and easy-to-use standby generator. Its combination of power output, advanced technology, and user-friendly features makes it an essential investment for anyone looking to ensure that they remain powered during outages.