Generac Power Systems 05176-0 owner manual Battery Maintenance, Adjusting Valve Clearance

Page 22

Section 5 — Maintenance

Air-cooled 15 kW Generators

5.7BATTERY MAINTENANCE

The battery should be inspected per the “Service Schedule”. The following procedure should be fol- lowed for inspection:

1.Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.

2.Check the battery fluid level of unsealed batteries and, if necessary, fill with DISTILLED WATER ONLY. DO NOT USE TAP WATER IN BATTER- IES.

3.Have the state of charge and condition checked. This should be done with an automotive-type bat- tery hydrometer.

Lead-acid batteries present a risk of fire because they generate hydrogen gas. The following pro- cedures are to be followed:

DO NOT SMOKE when near the battery;

DO NOT cause flame or spark in battery area; and

Discharge static electricity from body before touch- ing the battery by first touching a grounded metal surface.

Be sure the AUTO/OFF/MANUAL switch is set to the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.

DANGER

Do not dispose of the battery in a fire. The battery is capable of exploding.

A battery presents a risk of electrical shock

and high short circuit current. The following pre- cautions are to be observed when working on batteries:

Remove watches, rings or other metal objects;

Use tools with insulated handles;

Wear rubber gloves and boots;

Do not lay tools or metal parts on top of the battery; and

Disconnect charging source prior to connecting or disconnecting battery terminals.

Do not open or mutilate the battery. Released electrolyte has been known to be harmful to the skin and eyes, and to be toxic.

The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following procedures are to be observed:

Wear full eye protection and protective clothing;

Where electrolyte contacts the skin, wash it off immediately with water;

Where electrolyte contacts the eyes, immediately flush thoroughly with water and seek medical attention; and

Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) or water. The bicar- bonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.

Be sure the utility power supply is turned off, and the 5A fuse is removed from the generator control panel, or sparking may occur at the bat- tery posts as the cables are attached, causing an explosion.

5.8ADJUSTING VALVE CLEARANCE

After the first 50 hours of operation, adjust the valve clearance in the engine.

Important: If feeling uncomfortable about doing this procedure or the proper tools are not available, con- tact the nearest Authorized Dealer for service assis- tance. This is a very important step to insure longest life for the engine.

To adjust valve clearance:

Make sure the engine is at room temperature.

Make sure that the spark plug wire is removed from the spark plug and out of the way.

Remove the four screws attaching the valve cover with a #2 or #3 phillips screwdriver.

Make sure the piston is at Top Dead Center (TDC) of its compression stroke (both valves closed). To get the piston at TDC, remove the intake screen at the front of the engine to gain access to the fly- wheel nut. Use a large socket and socket wrench to rotate the nut and hence the engine. While watching the piston through the spark plug hole. The piston should move up and down. The piston is at TDC when it is up as high as it can go.

Loosen the rocker jam nut. Use an 10mm allen wrench to turn the pivot ball stud while checking clearance between the rocker arm and the valve stem with a feeler gauge. Correct clearance is 0.002-0.004 inch (0.05-0.1 mm). See Figure 5.6.

NOTE:

Hold the rocker arm jam nut in place as the pivot ball stud is turned.

20

Image 22
Contents Installation Introduction Authorized Dealer LocationSection Troubleshooting  Warning   Electrical Hazards  ‹ Standards IndexProtection Systems UNPACKING/INSPECTIONSystem SET LED Automatic Transfer Switch GeneratorFuel Requirements Recommendations SpecificationsReconfiguring Fuel System Fuel ConsumptionInstallation ‹ 2.1.1 Remote Monitoring Connections‹ 2.1.3 Transfer Switch Connection ‹ 2.1.2 Roof Open AlarmBattery Installation Before Initial START-UP Check Transfer Switch Operation BatteryElectrical Checks Generator Tests Under Load Adjusting the Regulator Natural GAS only Checking Automatic OperationVoltage Regulator Adjustment Engine Governor Adjustment‹ 4.1.1 Auto Position Sequence of Automatic OperationAutomatic Transfer Operation ‹ 4.1.3 Manual PositionManual Operation ‹ 4.4.1 Close to Normal Source Side‹ 4.4.2 Close to Emergency Source Side Voltage Checks‹ 4.4.3 Return to Normal Source Side ‹ 4.8.2 High Temperature Switch Setting the Exercise Timer‹ 4.8.1 LOW OIL Pressure Switch ‹ 4.8.3 Overcrank‹ 4.8.4 Overspeed Changing the Engine OILChecking the Engine OIL Level ‹ 5.3.1 Engine OIL RecommendationsChanging the OIL Filter Changing the Engine AIR CleanerSpark Plugs Battery Maintenance Adjusting Valve ClearanceCooling System OUT of Service Procedure‹ 5.12.1 Removal from Service Corrosion Protection‹ 5.12.2 Return to Service Service Maintenance Interval Information ‹ 7 KW 40 KW Small Standby Generator SetsMaintenance Level Level5 Tasks Maintenance Level Troubleshooting Guide Problem Cause CorrectionMounting Dimensions Electrical Data Control Panel BOX Transfer Switch 1VA GTS Exploded Views and Parts Lists Part NO. QTY. Description Air-cooled 15 kW Generators Control Panel Drawing No F5846 Description Exploded Views and Parts Lists Item Part NO. QTY. Description Exploded Views and Parts Lists Part NO. QTY Description Exploded QTY Description 7KW CASTING, Twin Regulator Housing Exploded Views and Parts Lists LUG Sldlss 250-#6 AL/CU MANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingGenerac Power Systems Standard Limited Warranty for

05176-0 specifications

Generac Power Systems 05176-0 is a powerful home standby generator designed to provide reliable backup power during outages. Known for its innovative technology and robust features, the 05176-0 model is part of Generac's Guardian Series, which is renowned for its reliability and ease of use.

One of the standout features of the Generac 05176-0 is its Generac G-Force engine, which is designed specifically for generator use. This automotive-grade engine is built to handle the rigors of prolonged operation, ensuring that homeowners have a dependable source of power. With a power output of 22 kW, it can handle the essential electrical loads of many homes, allowing users to power their lights, appliances, HVAC systems, and other necessary devices without interruption.

The 05176-0 comes equipped with a state-of-the-art transfer switch that automatically detects outages and begins the power restoration process within seconds. This automatic transfer switch eliminates the need for manual intervention, giving homeowners peace of mind that their power supply will seamlessly transition during a grid failure.

In terms of fuel efficiency, the Generac 05176-0 operates on either natural gas or liquid propane, providing flexibility for installation and operation. Its dual-fuel capability allows users to choose the fuel source that is most convenient and cost-effective for them.

Another notable feature is the generator’s Quiet-Test technology, which runs the generator at reduced RPMs for a self-test every week. This helps to ensure that the generator is operational and ready when needed while minimizing noise pollution in residential areas.

The model also boasts an intuitive LCD display that provides real-time information on the generator's status, including maintenance intervals and diagnostic information. This user-friendly interface simplifies monitoring and helps ensure that users can maintain optimal performance.

Moreover, the construction and design of the 05176-0 are intended for durability and weather resistance. With a robust enclosure made from high-quality materials, it is built to withstand harsh weather conditions, allowing homeowners to trust that their generator will perform reliably in any situation.

Overall, the Generac Power Systems 05176-0 stands out as a premium choice for homeowners seeking a reliable, efficient, and easy-to-use standby generator. Its combination of power output, advanced technology, and user-friendly features makes it an essential investment for anyone looking to ensure that they remain powered during outages.