Generac Power Systems 05176-0 Changing the OIL Filter, Changing the Engine AIR Cleaner

Page 21

Section 5 — Maintenance

Air-cooled 15 kW Generators

Figure 5.3 – Oil Drain Hose and Filter

Figure 5.4 — Engine Air Cleaner

Screw

Lo

 

os

 

e

 

n

 

Oil

Cover

Drain

 

Hose

 

Oil Filter

Filter

3.After the oil has drained, replace the cap onto the end of the oil drain hose. Retain the hose in the clip.

4.Refill with the proper recommended oil (see "Changing the Engine Oil"). See the "Specifications" section for oil capacities.

5.4CHANGING THE OIL FILTER

Change the engine oil filter as follows:

1.With the oil drained, remove the old oil filter by turning it counterclockwise.

2.Apply a light coating of clean engine oil to the gasket of the new filter. See the "Specifications" section for recommended filter.

3.Screw the new filter on by hand until its gasket lightly contacts the oil filter adapter. Then, tighten the filter an additional 3/4 to one turn (Figure 5.3).

4.Refill with the proper recommended oil (see "Changing the Engine Oil"). See the "Specifications" section for oil capacities.

5.Start the engine and check for leaks.

5.5CHANGING THE ENGINE

AIR CLEANER

See Figures 1.1 and 1.2, for the location of the air cleaner. Use the following procedure (Figure 5.4):

1.Turn the two screws counterclockwise to loosen.

2.Remove the cover and air filter.

3.Wipe away dust or debris from inside of the air box and around edges.

4.Install the new air cleaner into the air box.

5.Install the cover. Turn the two cover screws clock- wise to tighten.

See the “Service Schedule” section for air cleaner maintenance. See the "Specifications" section for air filter replacement part number.

5.6SPARK PLUG(S)

Reset the spark plugs gap or replace the spark plugs as necessary. See the “Service Schedule” section for maintenance requirements.

1.Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and commercial solvent. Do not blast the spark plugs to clean.

2.Remove the spark plugs and check the condition. Replace the spark plugs if worn or if reuse is questionable. See the “Service Schedule” section for recommended inspection.

3.Check the spark plug gap using a wire feeler gauge. Adjust the gap to 0.50 mm (0.020 inch) for by carefully bending the ground electrode (Figure 5.5).

Figure 5.5 – Setting the Spark Plug Gap

SET PLUG GAP AT 0.50 mm (0.020 inch)

19

Image 21
Contents Installation Authorized Dealer Location IntroductionSection Troubleshooting  Warning  ‹ Standards Index  Electrical Hazards UNPACKING/INSPECTION Protection SystemsSystem SET LED Generator Automatic Transfer SwitchReconfiguring Fuel System SpecificationsFuel Requirements Recommendations Fuel Consumption‹ 2.1.1 Remote Monitoring Connections Installation‹ 2.1.2 Roof Open Alarm ‹ 2.1.3 Transfer Switch ConnectionBattery Installation Check Transfer Switch Operation Battery Before Initial START-UPElectrical Checks Generator Tests Under Load Checking Automatic Operation Adjusting the Regulator Natural GAS onlyEngine Governor Adjustment Voltage Regulator AdjustmentAutomatic Transfer Operation Sequence of Automatic Operation‹ 4.1.1 Auto Position ‹ 4.1.3 Manual Position‹ 4.4.1 Close to Normal Source Side Manual OperationVoltage Checks ‹ 4.4.2 Close to Emergency Source Side‹ 4.4.3 Return to Normal Source Side ‹ 4.8.1 LOW OIL Pressure Switch Setting the Exercise Timer‹ 4.8.2 High Temperature Switch ‹ 4.8.3 OvercrankChecking the Engine OIL Level Changing the Engine OIL‹ 4.8.4 Overspeed ‹ 5.3.1 Engine OIL RecommendationsChanging the Engine AIR Cleaner Changing the OIL FilterSpark Plugs Adjusting Valve Clearance Battery Maintenance‹ 5.12.1 Removal from Service OUT of Service ProcedureCooling System Corrosion Protection‹ 5.12.2 Return to Service ‹ 7 KW 40 KW Small Standby Generator Sets Service Maintenance Interval InformationMaintenance Level Level5 Tasks Maintenance Level Problem Cause Correction Troubleshooting GuideMounting Dimensions Electrical Data Control Panel BOX Transfer Switch 1VA GTS Exploded Views and Parts Lists Part NO. QTY. Description Air-cooled 15 kW Generators Control Panel Drawing No F5846 Description Exploded Views and Parts Lists Item Part NO. QTY. Description Exploded Views and Parts Lists Part NO. QTY Description Exploded QTY Description 7KW CASTING, Twin Regulator Housing Exploded Views and Parts Lists LUG Sldlss 250-#6 AL/CU Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyGenerac Power Systems Standard Limited Warranty for

05176-0 specifications

Generac Power Systems 05176-0 is a powerful home standby generator designed to provide reliable backup power during outages. Known for its innovative technology and robust features, the 05176-0 model is part of Generac's Guardian Series, which is renowned for its reliability and ease of use.

One of the standout features of the Generac 05176-0 is its Generac G-Force engine, which is designed specifically for generator use. This automotive-grade engine is built to handle the rigors of prolonged operation, ensuring that homeowners have a dependable source of power. With a power output of 22 kW, it can handle the essential electrical loads of many homes, allowing users to power their lights, appliances, HVAC systems, and other necessary devices without interruption.

The 05176-0 comes equipped with a state-of-the-art transfer switch that automatically detects outages and begins the power restoration process within seconds. This automatic transfer switch eliminates the need for manual intervention, giving homeowners peace of mind that their power supply will seamlessly transition during a grid failure.

In terms of fuel efficiency, the Generac 05176-0 operates on either natural gas or liquid propane, providing flexibility for installation and operation. Its dual-fuel capability allows users to choose the fuel source that is most convenient and cost-effective for them.

Another notable feature is the generator’s Quiet-Test technology, which runs the generator at reduced RPMs for a self-test every week. This helps to ensure that the generator is operational and ready when needed while minimizing noise pollution in residential areas.

The model also boasts an intuitive LCD display that provides real-time information on the generator's status, including maintenance intervals and diagnostic information. This user-friendly interface simplifies monitoring and helps ensure that users can maintain optimal performance.

Moreover, the construction and design of the 05176-0 are intended for durability and weather resistance. With a robust enclosure made from high-quality materials, it is built to withstand harsh weather conditions, allowing homeowners to trust that their generator will perform reliably in any situation.

Overall, the Generac Power Systems 05176-0 stands out as a premium choice for homeowners seeking a reliable, efficient, and easy-to-use standby generator. Its combination of power output, advanced technology, and user-friendly features makes it an essential investment for anyone looking to ensure that they remain powered during outages.