Generac Power Systems 05176-0 Voltage Regulator Adjustment, Engine Governor Adjustment

Page 15

Section 3 — Post Installation Start-up and Adjustments

Air-cooled 15 kW Generators

7.Turn utility power to the main distribution panel back on. This can be done by switching the ser- vice main breaker to the on or closed position. Allow the generator to shut down.

Do not make any unnecessary adjustments. Factory settings are correct for most applica- tions. However, when making adjustments, be careful to avoid overspeeding the engine.

If this procedure or equipment are not available, locate the nearest Service Dealer and they can per- form the adjustments.

NOTE:

A service fee may be charged for this adjustment.

Figure 3.4 — V-twin Full Load Speed Adjust

Screw

Full Load Speed Adjust Screw

3.7ENGINE GOVERNOR ADJUSTMENT

If both AC frequency and voltage are correspondingly high or low, adjust the engine governor as follows:

1. Loosen governor clamp bolt (See Figure 3.3).

Figure 3.3 — V-twin Engine Governor

Adjustment

Idle Spring

Governor

Shaft

(Rotate Clockwise)

Governor Clamp Bolt

No Load Idle

Adjustment Screw

 

2.Completely remove the idle spring.

3.With governor arm at wide open throttle position, rotate governor shaft fully clockwise. Tighten clamp bolt to 84 inch-pounds.

4.Start unit and apply full load. Use full load speed adjust screw (Figure 3.4) to adjust frequency to 58 Hz.

5.Remove load, stop engine, loosen the idle adjust screw and reconnect the idle spring.

6.Using a hand, push the governor arm to the closed throttle position. Make sure the idle spring does not stretch at all.

7.Restart the unit.

8.Slowly turn the idle adjust screw to adjust the no- load idle frequency to 63-63.5 Hz.

9.The governor is now set.

‹3.7.1 ADDITIONAL CORROSION PROTECTION

Periodically spray all engine linkage parts and brack- ets with corrosion inhibiting spray such as WD-40®or a comparable product.

3.8VOLTAGE REGULATOR

ADJUSTMENT

With the frequency between 62-63.5 Hertz, slowly turn the slotted potentiometer (Figure 3.5) until line voltage reads 244-252 volts.

NOTE:

Remove the access panel on top of the control panel to adjust the voltage regulator.

Figure 3.5 – Voltage Adjustment Potentiometer

Turn to

adjust voltage.

NOTE:

The voltage regulator is housed above the generator's control panel. The regulator maintains a voltage in direct proportion to frequency. For example, at 62 Hertz, line-to-neutral voltage will be 124 volts.

13

Image 15
Contents Installation Authorized Dealer Location IntroductionSection Troubleshooting  Warning  ‹ Standards Index  Electrical Hazards UNPACKING/INSPECTION Protection SystemsSystem SET LED Generator Automatic Transfer SwitchFuel Consumption SpecificationsReconfiguring Fuel System Fuel Requirements Recommendations‹ 2.1.1 Remote Monitoring Connections Installation‹ 2.1.2 Roof Open Alarm ‹ 2.1.3 Transfer Switch ConnectionBattery Installation Check Transfer Switch Operation Battery Before Initial START-UPElectrical Checks Generator Tests Under Load Checking Automatic Operation Adjusting the Regulator Natural GAS onlyEngine Governor Adjustment Voltage Regulator Adjustment‹ 4.1.3 Manual Position Sequence of Automatic OperationAutomatic Transfer Operation ‹ 4.1.1 Auto Position‹ 4.4.1 Close to Normal Source Side Manual OperationVoltage Checks ‹ 4.4.2 Close to Emergency Source Side‹ 4.4.3 Return to Normal Source Side ‹ 4.8.3 Overcrank Setting the Exercise Timer‹ 4.8.1 LOW OIL Pressure Switch ‹ 4.8.2 High Temperature Switch‹ 5.3.1 Engine OIL Recommendations Changing the Engine OILChecking the Engine OIL Level ‹ 4.8.4 OverspeedChanging the Engine AIR Cleaner Changing the OIL FilterSpark Plugs Adjusting Valve Clearance Battery MaintenanceCorrosion Protection OUT of Service Procedure‹ 5.12.1 Removal from Service Cooling System‹ 5.12.2 Return to Service ‹ 7 KW 40 KW Small Standby Generator Sets Service Maintenance Interval InformationMaintenance Level Level5 Tasks Maintenance Level Problem Cause Correction Troubleshooting GuideMounting Dimensions Electrical Data Control Panel BOX Transfer Switch 1VA GTS Exploded Views and Parts Lists Part NO. QTY. Description Air-cooled 15 kW Generators Control Panel Drawing No F5846 Description Exploded Views and Parts Lists Item Part NO. QTY. Description Exploded Views and Parts Lists Part NO. QTY Description Exploded QTY Description 7KW CASTING, Twin Regulator Housing Exploded Views and Parts Lists LUG Sldlss 250-#6 AL/CU Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyGenerac Power Systems Standard Limited Warranty for

05176-0 specifications

Generac Power Systems 05176-0 is a powerful home standby generator designed to provide reliable backup power during outages. Known for its innovative technology and robust features, the 05176-0 model is part of Generac's Guardian Series, which is renowned for its reliability and ease of use.

One of the standout features of the Generac 05176-0 is its Generac G-Force engine, which is designed specifically for generator use. This automotive-grade engine is built to handle the rigors of prolonged operation, ensuring that homeowners have a dependable source of power. With a power output of 22 kW, it can handle the essential electrical loads of many homes, allowing users to power their lights, appliances, HVAC systems, and other necessary devices without interruption.

The 05176-0 comes equipped with a state-of-the-art transfer switch that automatically detects outages and begins the power restoration process within seconds. This automatic transfer switch eliminates the need for manual intervention, giving homeowners peace of mind that their power supply will seamlessly transition during a grid failure.

In terms of fuel efficiency, the Generac 05176-0 operates on either natural gas or liquid propane, providing flexibility for installation and operation. Its dual-fuel capability allows users to choose the fuel source that is most convenient and cost-effective for them.

Another notable feature is the generator’s Quiet-Test technology, which runs the generator at reduced RPMs for a self-test every week. This helps to ensure that the generator is operational and ready when needed while minimizing noise pollution in residential areas.

The model also boasts an intuitive LCD display that provides real-time information on the generator's status, including maintenance intervals and diagnostic information. This user-friendly interface simplifies monitoring and helps ensure that users can maintain optimal performance.

Moreover, the construction and design of the 05176-0 are intended for durability and weather resistance. With a robust enclosure made from high-quality materials, it is built to withstand harsh weather conditions, allowing homeowners to trust that their generator will perform reliably in any situation.

Overall, the Generac Power Systems 05176-0 stands out as a premium choice for homeowners seeking a reliable, efficient, and easy-to-use standby generator. Its combination of power output, advanced technology, and user-friendly features makes it an essential investment for anyone looking to ensure that they remain powered during outages.