Generac Power Systems 04389-3, 04456-3, 04390-3 owner manual Manual Transfer Operation

Page 18

Section 3 — Operation

Air-cooled 7 kW, 12 kW and 15 kW Generators

If utility source voltage drops below about 60 percent of the nominal supply voltage, the sensor energizes a 15-second timer.

Once the timer has expired, the engine will crank and start.

B.Engine Warm-up Time Delay

This mechanism lets the engine warm up for about 10 seconds before the load is transferred to the standby source.

C.Standby Voltage Sensor

This sensor monitors generator AC output volt- age. When the voltage has reached 50 percent of the nominal rated voltage, transfer to standby can occur.

D.Utility Voltage Pickup Sensor

This sensor monitors utility power supply volt- age. When that voltage is restored above 70 per- cent of the nominal source voltage, a retransfer time delay starts timing.

E.Retransfer Time Delay

This timer runs for about 15 seconds.

At end of a 15-second delay, circuit board action de-energizes transfer relay in the transfer switch.

Retransfer to utility power source then occurs.

F.Engine Cool-down Timer

When the load is transferred back to utility power source, the engine cool-down timer starts tim- ing.

The timer will run for about one minute, and the generator will then shut down.

3.5MANUAL TRANSFER OPERATION

‹3.5.1 TRANSFER TO GENERATOR POWER SOURCE

To start the generator and activate the transfer switch manually, proceed as follows:

1.Set the generator’s AUTO/OFF/MANUAL switch to OFF.

2.Set the generator’s main circuit breaker to its OFF (or open) position.

3.Turn OFF the utility power supply to the transfer switch using the means provided (such as a utility main line circuit breaker).

DANGER

Do not attempt to activate the transfer switch manually until all power voltage supplies to the switch have been positively turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possibly fatal elec- trical shock.

16

4.Use the manual transfer handle inside the trans- fer switch to move the main contacts to their “Standby” position, i.e., loads connected to the standby power source (Figure 3.2).

Figure 3.2 – Manual Transfer Switch Operation

5.To crank and start the engine, set the AUTO/OFF/ MANUAL switch to MANUAL.

6.Let the engine stabilize and warm up for a few minutes.

7.Set the generator’s main circuit breaker to its ON (or closed) position. The standby power source now powers the loads.

‹3.5.2 TRANSFER BACK TO UTILITY POWER SOURCE

When utility power has been restored, transfer back to that source and shut down the generator. This can be accomplished as follows:

1.Set the generator’s main circuit breaker to its OFF (or open) position.

2.Let the engine run for a minute or two at no-load to stabilize the internal temperatures.

3.Set the generator’s AUTO/OFF/MANUAL switch to its OFF (or open) position. The engine should shut down.

4.Check that utility power supply to the transfer switch is turned OFF.

DANGER

Do not attempt to activate the transfer switch manually until all power voltage supplies

to the switch have been positively turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possibly fatal electrical shock.

Image 18
Contents US Listed Introduction Authorized Dealer LocationTroubleshooting Post Installation Start-up AdjustmentsMaintenance Introduction Inside Front Cover Warning   Electrical Hazards  ‹ Standards IndexUNPACKING/INSPECTION Protection SystemsBreaker for Bedrooms Generator GfciSpecifications ‹ 1.5.1 Generator‹ 1.5.2 Engine Fuel Requirements Recommendations Reconfiguring the Fuel SystemSystem SET LED Fuel ConsumptionLocation ‹ 1.9.2 12KW and 15KW, V-TWIN Engines‹ 1.10.1 Generator ‹ 1.10.2 Transfer Switch Battery InstallationBattery 10.2.1 7 kW, 12 kW and 15 kW UnitsCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Generator Tests Under Load Checking Automatic OperationAdjusting the Regulator Natural GAS only Adjustment ScrewEngine Governor Adjustment ‹ 2.7.2 12 KW and 15 KW Units‹ 2.7.1 7 KW Units Voltage Regulator Adjustment BREAK-IN Procedure‹ 3.2.1 Auto Position Sequence of Automatic Operation ‹ 3.3.1 12 VDC Accessory OutletAutomatic Transfer Operation ‹ 3.2.2 OFF Position‹ 3.5.2 Transfer Back to Utility Power Source Manual Transfer Operation‹ 3.7.1 LOW OIL Pressure Switch Setting the Exercise Timer‹ 3.7.2 High Temperature Switch ‹ 3.7.3 OvercrankFuses Checking the Engine OIL Level‹ 3.7.4 Overspeed Changing the OIL Filter ‹ 4.3.2 OIL Change ProcedureChanging the Engine OIL ‹ 4.3.1 Engine OIL RecommendationsBattery Maintenance Spark PlugsValve Clearance Cooling System‹ 4.12.2 Return to Service OUT of Service Procedure‹ 4.12.1 Removal from Service Corrosion ProtectionService Schedule Be performed by the nearest Authorized DealerTroubleshooting Guide Problem Cause CorrectionAir-cooled 7 kW, 12 kW and 15 kW Generators Air-cooled 7 kW, 12 kW and 15 kW Generators Air-cooled 7 kW, 12 kW and 15 kW Generators Electrical Data Customer Connection Battery 1VA Engine Wiring Control Panel BOX Electronic Voltage Regulator Utility Electrical Data Electrical Data Electrical Data Electrical Data ATS N1A N2A Exploded Views and Parts Lists Part NO. QTY. Description Exploded Views and Parts Lists Part NO. QTY Description Exploded Views and Parts Lists QTY Description Exploded Views and Parts Lists COVER, 12 Circuit GTS Load Center 1310 Sleeve 124 125 139 136 135 123 120 137 143 133 134 132 KNOB, AIR Cleaner Exploded Views and Parts Lists QTY 32 31 Stator 12KW Exploded Views and Parts Lists PIN, Piston D20 Exploded Views and Parts Lists SCREW, Taptite M6-1.0X8 Yellow Chrome 7KW Mounting Dimensions Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule

04389-3, 04456-3, 04390-3 specifications

Generac Power Systems has established itself as a leading name in power generation equipment, and models 04389-3, 04456-3, and 04390-3 exemplify the company’s commitment to reliability and technology. These models are particularly popular among homeowners and businesses that need dependable backup power solutions.

The Generac 04389-3 is a 22 kW standby generator designed to provide seamless power during outages. It boasts a powerful 999cc engine that can handle heavy loads, making it suitable for larger homes or commercial settings. The generator features Generac’s patented True Power Technology, which ensures clean and stable power delivery, making it safe for sensitive electronics. It also comes equipped with an innovative shutdown system that prevents damage during low oil conditions and features a five-year limited warranty for added peace of mind.

Similarly, the 04456-3 model also serves as a robust standby generator, offering 24 kW of power output. This model highlights an advanced alternator that provides a reliable source of energy for running essential appliances like refrigerators, air conditioners, and heating systems. The 04456-3 includes an automatic exercise mode, allowing it to run tests periodically to ensure it’s always ready to operate when needed. Additionally, it utilizes a user-friendly digital controller that simplifies monitoring and operational management.

The Generac 04390-3 model offers a slightly lower output at 20 kW but retains high efficiency and reliability. Like its counterparts, it features an innovative design that operates quietly while delivering consistent power. This model is particularly aimed at residential users who require dependable backup solutions without the noise commonly associated with generators. It incorporates Generac’s Smart Management modules, enabling users to manage power loads effectively and avoid overloading the system.

All three models benefit from Generac’s Mobile Link technology, which enables remote monitoring via mobile devices. This feature allows users to check the status of their generators, including maintenance alerts and operational history, providing a convenient way to manage energy needs. In summary, Generac models 04389-3, 04456-3, and 04390-3 offer cutting-edge features, dependable technology, and robust capabilities, making them an ideal choice for anyone seeking reliable backup power solutions.