Section 1 — General Information

Air-cooled 7 kW, 12 kW and 15 kW Generators

1.6SYSTEM SET LED

The “System Set” LED is lit when all of the following conditions are true:

1.The AUTO/OFF/MANUAL switch is set to the AUTO position.

2.The utility voltage being supplied to the unit is being sensed by the PCB. If the utility sense volt- age is not connected to the unit or if it is below 168 volts AC, then the system set light will flash rapidly. This indicates that if the AUTO/OFF/ MANUAL switch is placed in the Auto position, the generator will start.

3.The “Not In Auto” dip switch is set to the OFF position on the control board.

4.No alarms are present, for example, low oil pres- sure, high temperature, etc.

1.7FUEL REQUIREMENTS

AND RECOMMENDATIONS

With LP gas, use only the vapor withdrawal system. This type of system uses the vapors formed above the liquid fuel in the storage tank.

The engine has been fitted with a fuel carburetion system that meets the specifications of the 1997 California Air Resources Board for tamper-proof dual fuel systems. The unit will run on natural gas or LP gas, but it has been factory set to run on natural gas. Should the primary fuel need to be changed to LP gas, the fuel system needs to be reconfigured. See Section 1.9 for instructions on reconfiguration of the fuel system.

Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.

Required fuel pressure for natural gas is 5 inches to 7 inches water colum (0.18 to 0.25 psi); and for liquid propane, 10 inches to 12 inches of water column (0.36 to 0.43 psi).

DANGER

Gaseous fuels such as natural gas and liquid propane (LP) gas are highly explosive. Even the slightest spark can ignite such fuels and cause an explosion. No leakage of fuel is permitted. Natural gas, which is lighter than air, tends to collect in high areas. LP gas is heavier than air and tends to settle in low areas.

1.9RECONFIGURING THE FUEL SYSTEM

‹1.9.1 7 KW, 410CC ENGINE

To reconfigure the fuel system from NG to LP, follow these steps (Figure 1.3):

NOTE:

The primary regulator for the propane supply is NOT INCLUDED with the generator. A fuel pres- sure of 10 to 12 inches of water column (0.36 to

0.43psi) to the fuel inlet of the generator MUST BE SUPPLIED.

1.Turn off the main gas supply (if connected).

2.Open the roof and remove the door.

3.Remove the battery (if installed).

4.Disconnect wire #0 and wire #14 from the gas solenoid on top of the demand regulator.

5.Remove the carburetor fuel hose from the outlet port of the demand regulator.

6.Remove the demand regulator by removing the fastener that retains the regulator mounting bracket.

7.Remove the square headed steel pipe plug from outlet port #1 and the brass hose barb fitting from outlet port #2.

Figure 1.3 – Demand Regulator

NOTE:

Any piping used to connect the generator to the fuel supply should be of adequate size to ensure the fuel pressure NEVER drops below 4 inches water colum for natural gas or 10 inches water column for liquid propane for all load ranges.

1.8FUEL CONSUMPTION

 

Model #

Nat. Gas (*)

LP Vapor (**)

 

 

 

1/2 Load

Full Load

1/2 Load

Full Load

 

 

04389

66

119

0.82/30

1.47/54

 

 

04456

152

215

1.53/56

2.08/76

 

 

04390

156

220

1.58/58

2.40/88

 

FUEL HOSE

BRASS HOSE FITTING

ADJUSTMENT SCREW

HOSE & PLUG

SWITCHED SIDES

PIPE

FUEL HOSE

PLUG

 

BRASS HOSE

FITTING

OUTLET

PORT

FUEL JET

*Natural gas is in cubic feet per hour.

**LP is in gallons per hour/cubic feet per hour.

*** Values given are approximate.

NG FUEL SYSTEM

LP FUEL SYSTEM

7

Image 9
Contents US Listed Authorized Dealer Location IntroductionMaintenance Post Installation Start-up AdjustmentsTroubleshooting Introduction Inside Front Cover Warning  ‹ Standards Index  Electrical Hazards UNPACKING/INSPECTION Protection SystemsBreaker for Bedrooms Gfci GeneratorSpecifications ‹ 1.5.1 Generator‹ 1.5.2 Engine System SET LED Reconfiguring the Fuel SystemFuel Requirements Recommendations Fuel ConsumptionLocation ‹ 1.9.2 12KW and 15KW, V-TWIN Engines‹ 1.10.1 Generator Battery Battery Installation‹ 1.10.2 Transfer Switch 10.2.1 7 kW, 12 kW and 15 kW UnitsCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Checking Automatic Operation Generator Tests Under LoadAdjustment Screw Adjusting the Regulator Natural GAS onlyEngine Governor Adjustment ‹ 2.7.2 12 KW and 15 KW Units‹ 2.7.1 7 KW Units Voltage Regulator Adjustment BREAK-IN Procedure‹ 3.2.1 Auto Position Automatic Transfer Operation ‹ 3.3.1 12 VDC Accessory OutletSequence of Automatic Operation ‹ 3.2.2 OFF PositionManual Transfer Operation ‹ 3.5.2 Transfer Back to Utility Power Source‹ 3.7.2 High Temperature Switch Setting the Exercise Timer‹ 3.7.1 LOW OIL Pressure Switch ‹ 3.7.3 OvercrankFuses Checking the Engine OIL Level‹ 3.7.4 Overspeed Changing the Engine OIL ‹ 4.3.2 OIL Change ProcedureChanging the OIL Filter ‹ 4.3.1 Engine OIL RecommendationsSpark Plugs Battery MaintenanceCooling System Valve Clearance‹ 4.12.1 Removal from Service OUT of Service Procedure‹ 4.12.2 Return to Service Corrosion ProtectionBe performed by the nearest Authorized Dealer Service ScheduleProblem Cause Correction Troubleshooting GuideAir-cooled 7 kW, 12 kW and 15 kW Generators Air-cooled 7 kW, 12 kW and 15 kW Generators Air-cooled 7 kW, 12 kW and 15 kW Generators Electrical Data Customer Connection Battery 1VA Engine Wiring Control Panel BOX Electronic Voltage Regulator Utility Electrical Data Electrical Data Electrical Data Electrical Data ATS N1A N2A Exploded Views and Parts Lists Part NO. QTY. Description Exploded Views and Parts Lists Part NO. QTY Description Exploded Views and Parts Lists QTY Description Exploded Views and Parts Lists COVER, 12 Circuit GTS Load Center 1310 Sleeve 124 125 139 136 135 123 120 137 143 133 134 132 KNOB, AIR Cleaner Exploded Views and Parts Lists QTY 32 31 Stator 12KW Exploded Views and Parts Lists PIN, Piston D20 Exploded Views and Parts Lists SCREW, Taptite M6-1.0X8 Yellow Chrome 7KW Mounting Dimensions Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyWarranty Schedule

04389-3, 04456-3, 04390-3 specifications

Generac Power Systems has established itself as a leading name in power generation equipment, and models 04389-3, 04456-3, and 04390-3 exemplify the company’s commitment to reliability and technology. These models are particularly popular among homeowners and businesses that need dependable backup power solutions.

The Generac 04389-3 is a 22 kW standby generator designed to provide seamless power during outages. It boasts a powerful 999cc engine that can handle heavy loads, making it suitable for larger homes or commercial settings. The generator features Generac’s patented True Power Technology, which ensures clean and stable power delivery, making it safe for sensitive electronics. It also comes equipped with an innovative shutdown system that prevents damage during low oil conditions and features a five-year limited warranty for added peace of mind.

Similarly, the 04456-3 model also serves as a robust standby generator, offering 24 kW of power output. This model highlights an advanced alternator that provides a reliable source of energy for running essential appliances like refrigerators, air conditioners, and heating systems. The 04456-3 includes an automatic exercise mode, allowing it to run tests periodically to ensure it’s always ready to operate when needed. Additionally, it utilizes a user-friendly digital controller that simplifies monitoring and operational management.

The Generac 04390-3 model offers a slightly lower output at 20 kW but retains high efficiency and reliability. Like its counterparts, it features an innovative design that operates quietly while delivering consistent power. This model is particularly aimed at residential users who require dependable backup solutions without the noise commonly associated with generators. It incorporates Generac’s Smart Management modules, enabling users to manage power loads effectively and avoid overloading the system.

All three models benefit from Generac’s Mobile Link technology, which enables remote monitoring via mobile devices. This feature allows users to check the status of their generators, including maintenance alerts and operational history, providing a convenient way to manage energy needs. In summary, Generac models 04389-3, 04456-3, and 04390-3 offer cutting-edge features, dependable technology, and robust capabilities, making them an ideal choice for anyone seeking reliable backup power solutions.