DeviceNet Network Scanner DVPDNET-SL

DVPDNET

DVP28SV

RUN

STOP

35mm DIN rail

3.3Connecting to DeviceNet Connection Port

„The colors on the PINs on the DeviceNet connection port match the colors of the connection cables. Make sure you connect the cable to the right PIN.

„We recommend you also apply Delta’s power module in the connection.

4 Configuration

4.1Corresponding Relation between DVPDNET-SL and DVP-SV

After all DVPDNET-SL are connected to DVP-SV, DVP-SV will distribute data mapping areas to every

DVPDNET-SL.

DVPDNETDVP28SV

RUN

STOP

The index of DVPDNET-SL is its number. The first DVPDNET-SL on the left hand side of DVP-SV is No. 1, the following DVPDNET-SL modules are No.2, No.3, No.4 and so on.

DVPDNET-SL

Mapped D registers

index

Output mapping

Input mapping

1

D6250 ~ D6497

D6000 ~ D6247

 

 

 

2

D6750 ~ D6997

D6500 ~ D6747

 

 

 

3

D7250 ~ D7497

D7000 ~ D7247

 

 

 

8

DVP-PLC Operation Manual

Page 10
Image 10
2nd Ave DVP-0204520-02 operation manual Configuration, Connecting to DeviceNet Connection Port