DeviceNet Network Scanner DVPDNET-SL

Item

Function

Default

DIDO Output

The digital output points shall be 8’s multiple. The number will

 

be regarded as 8 when it is less than 8 and regarded as 16

N/A

Points (Y)

when it is bigger than 8 but less than 16.

 

 

 

 

 

 

AIAO Module

The number of special I/O modules connected to RTU-DNET.

N/A

Number

Range: 0 ~ 8

 

 

 

 

Diagnostic

The interval when RTU-DNET executes diagnosis. Range:

5 (sec)

Intervel Time

1~ 65 secs

 

 

 

 

IO Module

How RTU-DNET will react when the special I/O module

 

connected to it is offline. You can choose “Ignored”, "Alarm”

Alarm

Offine Treatment

or “stop DeviceNet IO".

 

 

 

 

 

 

IO Module

How RTU-DNET will react when it detects errors. You can

Alarm

Error Treatment

choose “Ignored”, “Alarm” or “Stop DeviceNet IO”.

 

 

 

 

 

For you to decide whether to add control word and status

 

 

word to I/O data. When you choose not to do it, the I/O data

 

Add control word

in RTU-DNET and DeviceNet master will not include control

Not to add

and status word to

IO data

word and status word. If you choose to add them in, the I/O

 

 

data in RTU-DNET and DeviceNet master will include control

 

 

word and status word.

 

 

 

 

(13)Confirm all the configurations are correct and click on “Download” to download the configurations to RTU-DNET. After the download is completed, click on “OK”.

(14)After the configuration o f RTU-DNET is completed, you will return to the main page.

(15) Double click on VFD-B Drives (node 03), and the “Node Configuration…” dialog box will appear.