DeviceNet Network Scanner DVPDNET-SL

(4)Program explanations:

„In the beginning of the program, clear the response message editing area and request message editing area to 0.

„When M0 = On, DVPDNET-SL will send out request message, reading Class 1>>Instance 1>> Attribute 1 of the target equipment (node address: 02). If the communication of explicit message is successful, the slave will return with a response message.

„When M0 = On, DVPDNET-SL will only send out request message once. If you would like it to sendout request message again, you will have to change ReqID.

„When the reading is successful, the message responded from the target equipment will be stored in D6000 ~ D6003.

5.Application example (II)

Target

M1 = On, set 0x99>>Instance 1>>Attribute 2 of IFD9502 to “0004Hex”.

(1)The connection

(2) Compulsory settings and explanations on devices „ Compulsory settings in DVPDNET-SL

 

Parameter

Set value

Explanation

 

Node address

00

Set the node address of DVPDNET-SL to “00”.

 

 

 

 

 

Baud rate

500kbps

Set the communication speed of DVPDNET-SL and bus to

 

“500kbps”.

 

 

 

„ Compulsory settings in IFD9502

 

 

 

 

 

 

Parameter

Set value

Explanation

 

Node address

02

Set the node address of IFD9502 to “02”.

 

 

 

 

 

Baud rate

500kbps

Set the communication speed of IFD9502 and bus to

 

“500kbps”.

 

 

 

„ Compulsory settings in VFD-B

 

 

 

 

 

 

Parameter

Set value

Explanation

 

02-00

04

The main frequency is operated on RS-485 interface.

 

 

 

 

24