Using Optional Power Systems
You can connect a UPS unit to an Advanced RPS unit as long as you do not exceed the maximum wattage (325 watts) for the UPS unit. To verify that the UPS unit’s maximum wattage is not exceeded, calculate the total power consumption of all units connected to the Advanced RPS. If the result is less than 325 watts, your configuration is safe; if the result is greater than 325 watts, then there are too many units connected to the Advanced RPS.
To calculate the total power consumption of all units connected to the Advanced RPS:
1Calculate the total wattage of all the units connected to the Advanced RPS.
For example, one Hub 1000 SX has a maximum power consumption of 65 watts; two Hub 1000 SX units have a maximum power consumption of 130 watts, and so forth.
2Divide the total wattage of all units by 0.7, which is the efficiency rating (70%) of the Advanced RPS.
If the result is less than 325 watts, your configuration is safe; if the result is higher, then there are too many units connected to the Advanced RPS.