3M 7625-T-110 Install Lug or Connector, Ground Braid, 1st Scotch Mastic Strip 2230 Solder Block

Models: 7625-T-110 7623-T-110 7624-T-110 7622-T-110 7626-T-110

1 20
Download 20 pages 50.98 Kb
Page 14
Image 14
1st Scotch® Mastic Strip 2230 Solder Block

Constant Force Spring Shield Wires

Ground Braid

1st Scotch® Mastic Strip 2230 Solder Block

2nd Scotch® Mastic Strip 2230

Trim

Cable

Wire

Shield

Ground Braid Leg Trim

Figure 21

13.5Wrap two highly stretched half-lapped layers of electrical grade vinyl tape around mastic seal, constant force spring and exposed shield wires (Figure 22).

NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 1" (25 mm) must be exposed.

1-1/2" (38 mm)

Semi-Con

Shield Wires

Constant Force Spring

Two Half-Lapped Layers of Electrical Grade Vinyl Tape

Scotch® Mastic Strip 2230

Vinyl Tape Marker

Figure 22

14.0 Install Lug or Connector

Important Packaging Notice

In order to make sure that you receive an undamaged termination, this 3M™ Cold Shrink QT-III Termination is packed with a RED SHIPPING CORE inside of the white core. Please remove the red shipping core BEFORE you install the termination. This shipping core can be recycled with other polypropylene waste.

14.1Check to insure 3MCold Shrink QT -III Silicone Rubber Termination fits over the selected lug or connector. If lug or connector (Figure 23) will not fit through the termination core, clean the insulation (per Step 15.0) and slide termination on cable before installing lug or connector. DO NOT REMOVE CORE AT THIS TIME.

Clearance

Connector/Lug

Figure 23

14

78-8113-5099-6 Rev E

Page 14
Image 14
3M 7625-T-110 Install Lug or Connector, Ground Braid, 1st Scotch Mastic Strip 2230 Solder Block, 2nd Scotch Mastic Strip