Installation | is |
|
Air humidity and ambient temperature
The boiler room must be
Air humidity and ambient temperature specifications
Air humidity and ambient temperature
Air humidity | max. 93% RV at +25°C |
|
|
Ambient temperature | Functional: 0 < T < 60°C |
|
|
3.3.2Maximum floor load
Allow for the appliance's weight with respect to the maximum floor load; refer to the table.
Weight specifications related to maximum floor load
Weight of the appliance filled with water
BFC 80, BFC 100
940 kg
3.3.3Water composition
The appliance is intended for heating drinking water. The drinking water must comply with the regulations governing drinking water for human consumption. The table gives an overview of the specifications.
Water specifications
Water composition
Hardness | > 1.00 mmol/l: |
(alkaline earth ions) | • German hardness> 5.6° dH |
| • French hardness > 10.0° fH |
| • English hardness > 7.0° eH |
|
|
Conductivity | > 125 µS/cm |
|
|
Acidity (pH value) | 7.0 < pH value < 9.5 |
|
|
|
|
Note
If the water specifications deviate from those stated in the table, then the tank protection cannot be guaranteed (16 "Warranty (certificate)").
3.3.4Working clearances
For access to the appliance it is recommended that the following clearances are observed (see figure):
•AA: around the appliance's control column and cleaning openings: 100cm.
•BB: all sides of the appliance: 50cm.
Note
When installing the appliance, be aware that any leakage from the tank
and/or connections can cause damage to the immediate environment or floors below the level of the boiler room. If this is the case, then the appliance should be installed above a wastewater drain or in a suitable metal leak tray.
The leak tray must have an appropriate wastewater drain and must be at least 5cm deep with a length and width at least 5 m greater than the diameter of the appliance.
18 | Instruction manual BFC |