A.O. Smith BFC -100, BFC - 80 service manual Performing maintenance

Models: BFC - 80 BFC -100

1 96
Download 96 pages 7.52 Kb
Page 84
Image 84

15

Performing maintenance

s

 

n

 

min

 

 

0063

O

I

 

IMD-0423 R0

6.Switch the electronic controller ON by setting the ON/OFF switch to position I.

INTERNAL CHECK

The display will now show INTERNAL CHECK for about 10 seconds, and will then go to the main menu.

MENU »OFF ^ ON

ÈWEEK PROGRAM

7.Activate "ON mode" by going through the following steps:

-Press once on the blue arrow () to position the cursor beside ON,

then press .

-Confirm the selection START OPERATION with .

8.If there is no heat demand, increase Tset (11.3 "Setting the water temperature"). Note the original setting. Draw some hot water off to create heat demand.

9.Check whether the heating cycle runs correctly (9.3 "The appliance's heating cycle").

10.If you have adjusted Tset , return it to the desired value (11.3 "Setting the water temperature").

11.Remove the plastic cover on the top of the appliance.

12.Check the supply and burner pressure (3.11 "Checking the supply pressure and burner pressure"), and adjust them if necessary.

13.Check that all components of the chimney flue system are properly attached.

14.Check the pressure differential across the orifice plate of the pressure switch (see the table). If the pressure difference is too low, the heat exchanger must be cleaned (15.4.4 "Cleaning the heat exchanger").

Pressure switch pressure differential

Appliance

Observed pressure differential across the pressure switch

 

(Pa)

 

 

BFC 80

> 1005

 

 

BFC 100

> 1145

 

 

15.Test the operation of the overflow valve of the protected cold supply setup. The water should spurt out.

16.Test the overflow operation of the T&P valve. The water should spurt out.

84

Instruction manual BFC

Page 84
Image 84
A.O. Smith BFC -100, BFC - 80 service manual Performing maintenance