Locating the New Water Heater (cont’d)
Combustion Air and Ventilation for Appliances Located in Confined Spaces
Confined Space is a space whose volume is less than 50 cubic feet per 1,000 Btu per hour of the aggregate input rating of all appliances installed in that space.
a.ALL AIR FROM INSIDE BUILDINGS: (See Page 8 Figure 1, and Figure 6 below)
The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each open- ing shall have a minimum free area of one square inch per 1,000 BTU per hour of the total input rating of all gas utiliza- tion equipment in the confined space, but not less than 100 square inches. One opening shall commence within 12 inch- es of the top and one commencing within 12 inches of the bottom of the enclosure.
VENT THROUGH
ROOF
VENT TO
OUTDOORS
OPENINGSWATER
HEATER
Figure 6
b. ALL AIR FROM OUTDOORS: (see Figures 7-9)
The confined space shall be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches from the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
VENTILATION LOUVERS |
| VENT THROUGH | |
(each end of attic) |
| ||
|
|
| ROOF |
|
|
| VENT TO |
|
|
| OUTDOORS |
|
|
| |
| INLET AIR | WATER |
|
| HEATER |
| |
| DUCT |
| |
|
|
|
Figure 7
VENTILATION LOUVERS
1.When directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equip- ment in the enclosure. (See Figure 6.)
2.When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure. (See Figure 8.)
VENTILATION LOUVERS
(each end of attic)
|
|
|
|
|
| VENT THROUGH ROOF | |
|
|
|
|
|
|
| |
| AIR OUTLET |
|
|
| VENT TO | ||
|
|
|
|
|
|
| OUTDOORS |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
|
|
|
|
|
| WATER |
|
|
|
|
|
|
|
| |
INLET AIR DUCT |
|
|
| HEATER |
| ||
|
|
|
|
| |||
(ends 1″ above floor) |
|
|
|
| |||
|
| ||||||
|
|
|
|
|
|
|
|
Figure 8
3.When communicating with the outdoors through horizon- tal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 BTU per hour of total input rating of all equipment in the enclosure. (See Figure 9.)
VENT THROUGH
ROOF
VENT TO
OUTDOORS
OUTLET AIR DUCT
INLET AIR DUCT
Figure 9
4.When ducts are used, they shall be of the same
5.Louvers and Grilles: In calculating free area, consideration shall be given to the blocking effect of louvers, grilles or screens protecting openings. Screens used shall not be small- er than 1⁄4 inch mesh. If the free area through a design of lou- ver or grille is known, it should be used in calculating the size opening required to provide the free area specified. If the design and free area is not known, it may be assumed that wood louvers will be
6.Special Conditions Created by Mechanical Exhausting or Fireplaces: Operation of exhaust fans, ventilation systems, clothes dryers or fireplaces may create conditions requiring special attention to avoid unsatisfactory operation of installed gas utilization equipment.