FLUE PRODUCTS
MAKE | HOLE HERE |
|
|
|
|
|
|
| ||
FOR C02 MEASUREMENT, |
|
|
|
|
|
|
| |||
SMOKE AND TEMPERATURE |
|
|
|
|
|
|
| |||
READINGS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
SEAL Vv1TH RTV SILICONE |
|
|
|
|
|
|
| |||
APPROXIMATELY 18' ABOVE |
|
|
|
|
| • |
| |||
CENTERLINE OF TEE |
|
|
|
|
|
| ||||
|
|
|
|
|
|
| ||||
DO NOT USE CEMENT |
|
|
|
|
|
|
| |||
AT METAL COLLAR |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |||
STAINLESS/RUBBER |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||||
QUICK CONNECT COUPLER |
|
|
|
|
|
|
| |||
CONDENSATE COLLECTOR |
|
|
|
|
|
|
| |||
VENT TO ATMOSHPERE |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |||
PREFILL TRAP \\1TH WATER |
|
|
|
|
|
|
| |||
CONDENSATE NEUTRALIZER | \ |
|
|
|
|
| ||||
NEUTRALIZER MUST LAY |
|
|
|
|
|
|
| |||
HORIZONTALLY | . |
|
|
|
|
| ||||
REPLACE AT THE BEGINNING |
|
|
|
|
|
|
| |||
OF EACH HEATING SEASON |
|
|
|
|
|
|
|
TO FLOOR DRAIN
OR CONDENSATE PUMP
I
COMBUSTION AIR
BURNER
VESTIBULE
BLOWER
SECTION
Note:
Furnace maybe vented from left or right side.
IX. OIL LINE
GENERAL
The furnace rating plate includes the approved furnace input rating and fuel types. The furnace must be equipped to operate on the type of oil applied.
CAUTION I
TO PREVENT UNRELIABLE
OPERATION OR EQUIPMENT
DAMAGE, THE OIL LINE PRESSURE
MUST BE SET AT 140 P.S.I.
OIL TANK
Oil storage tanks must be selected and installed in compliance with applicable codes; in the United States, NFPA 31,
Standard for the Installation of Oil Burning Equipment. Chapter 2, and in Canada, CANlCSA B139, Installation Code for Oil Burning Equipment. Section 6. Observe all local codes and
The fill pipe must be no less than 2 inches I.P.S., and terminate with an appropriate cap in a location where debris will not enter the fill pipe during oil delivery.
If located indoors, the tank should normally be in the lowest level, (cellar, basement, etc.). it must be equipped with a
PIPING INSTALLATION
In the United States, NFPA 31, Standard for the Installation of Oil Burning EqUipment. Chapter 2.
In Canada, the entire fuel system should be installed in accordance with the reqUirements of CAN/CSA B139, and local regulations. Use only approved fuel oil tanks, piping, fittings, and oil filters.
Ensure that all fittings used in a copper oil line system are high quality flare fittings. Do not use compression fittings. Do not use Teflon tape on any fittings.
Pressurized or gravity feed installations must not exceed 3 PSIG. Pressures greater than 10 PSIG may cause damage to the shaft seal. If the height of the oil stored in a tank above the oil burner exceeds
11% feet, it may be necessary to use a pressure regulating device approved for this purpose.
15