Circulator Blower Speeds
Low | Red |
Medium | Blue |
|
|
Hiah | Black |
Common/Neutral | White |
|
|
XII. NORMAL SEQUENCE OF
OPERATION
POWER UP MODE
The normal power up sequence is as follows:
•115 VAC power applied to furnace
•Furnace awaits call from thermostat
HEATING MODE
The normal operational sequence in heating mode is as follows:
•Rand W thermostat contacts close, initiating a call for heat
Closure of the thermostat switch through relay #1 energizes primary control on the burner. Primary control goes in the
Blower operation is controlled by Blower Delay
With factory setting (DELAY ON MAKE) of (30 sec), approximately 30 seconds after burner ignites, blower relay energizes to run comfort blower in the heating speed mode.
NOTE:
Blower speed (heating) is factory set on high speed.
THERMOSTAT SATISFIED
When the thermostat satisfied, heat contact opens through relay No.1, primary control relay drops out, which
FAN ONLY MODE
The normal operational sequence in fan only mode is as follows:
•Rand G thermostat contacts close, initiating a call for fan
•Circulator blower is energized
•Circulator blower runs
•Rand G thermostat contacts open, completing the call for fan
•Circulator blower is
•Furnace awaits next call from thermostat
COOLING MODE
When the
XIII. TROUBLESHOOTING
IMPORTANT:
DUE TO THE POTENTIAL HAZARD OF LINE VOLTAGE, ONLY A TRAINED, EXPERIENCED SERVICE TECHNICIAN SHOULD PERFORM THE TROUBLESHOOTING PROCEDURE.
PRELIMINARY STEPS:
Check the diagnostic light for indications of burner condition. Refer to R7184 LED Diagnostic Light section for details.
CAUTION!
When simulating a call for heat at the R7184, disconnect at least one thermostat lead wire from the T - T/3 terminals to prevent damage to the thermostat. Neglecting this procedure may burn out the heat anticipator of a standard 24 VAC thermostat, or cause harm to components of a micro electronic thermostat.
19