Drill a 3/8" hole in the PVC exhaust vent piping approximately 18" above where the PVC exits the side of the furnace for your combustion analysis equipment. (Seal with RTV silicone when finished conducting combustion analysis).
BURNER ADJUSTMENT
1)Operate burner for 15 minutes before conducting test work.
2)Adjust burner settings until a trace
3)Read C02%. This should be approximately 13.0%.
4)Increase air to burner to reduce C02% 1.0 to 1.5% less than where you were able to obtain a trace of smoke.
This procedure allows a margin of reserve for variable conditions.
5)
Your final C02% should be approximately 11.5%
Check vent stack temperatures as below:
M | APPROX. | INPUT | THERMAL | |
AMBIENT | RATE | EFFICIENCY | ||
0 | ||||
D | PLUS |
|
| |
STACK |
|
| ||
E |
|
| ||
TEMP F. |
|
| ||
L |
|
| ||
|
|
| ||
|
|
|
| |
50 | 58,000 | |||
75 | 82,000 | |||
|
|
|
| |
100 | 100,000 | |||
125 | 115,000 | |||
|
|
|
|
Temperature Rise
Temperature rise must be within the range below. An incorrect temperature rise may result in condensing in or overheating of the heat exchanger.
Determine and adjUst temperature rise as
follows:
Model | Temp. F. |
| Degree Rise |
|
|
|
|
|
|
|
|
1.Operate furnace with burner firing for approXimately ten minutes. Ensure all registers are open and all duct dampers are in their final (fully or partially open) position.
2.Place thermometers in the return and supply ducts as close to the furnace as possible. Thermometers must not be influenced by radiant heat by being able to "see" the heat exchanger
HEAT EXCHANGER
RADIATION "LINE OF SIGHT"
~ SUPPLY
L..,/ AIR
iT'U""
Temperature Rise Measurement
3.Subtract the return air temperature from the supply air temperature to determine the air temperature rise. Allow adequate time for thermometer readings to stabilize.
4.Adjust temperature rise by adjusting the circulator blower speed. Increase blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise.
Set thermostat heat anticipator setting at 0.2 A as a base point. Operate furnace and measure anticipation amperage and adjust thermostat to manufacturer's instructions.
CIRCULATOR BLOWER SPEEDS
This furnace is equipped with a
To adjust the circulator blower speed, proceed as follows:
1.Turn OFF power to the furnace.
2.Relocate desired motor leads to the circulator blower terminals on the terminal block as required.
3.Turn ON power to furnace.
4.Verify proper temperature rise as outlined in Section XIV, Startup Procedure and Adjustment - Temperature Rise.
18