LTPH-UM-1049-02, Issue 2 Provisioning
H2TU-C-319 List 4E January 9, 2002 11
Resetting to Factory Default Values
All user options for the H2TU-C, described in Table 5 on page 18, can be set to the factory default values using
the MODE and LBK pushbuttons. To set the user options to their default values:
1Press the LBK pushbutton for 6 seconds until the following message appears:
DFLT NO
2Press the LBK pushbutton until the DFLT NO message is displayed.
The message changes to DFLT YES indicating the factory default values are now in effect and the display
returns to the normal mode.
To terminate the DFLT mode without setting the factory default values, do one of the following:
Press the MODE pushbutton to return to the normal display mode.
Wait 30 seconds for the unit to return to the normal display mode.
Displaying System Parameter Settings
To scroll through the current settings of all system parameters, press the MODE pushbutton for 3 or more seconds.
The H2TU-C displays the following parameters:
H2TU-C software version number
H2TU-C list number
Type of frame pattern received from the DSX-1
Line code of the signal received from the DSX-1
All user-configured parameter settings
Loop attenuation threshold setting
Margin alarm threshold setting
Disabling an Alarm
System alarms can be disabled by pressing the LBK pushbutton on the H2TU-C front panel. This executes an
ACO and returns the H2TU-C to its non-alarm state. For more information, see Retiring System Alarms on
page53.
Loopback Modes
See Loopback Operation on page 55 for instructions on using the MODE and LBK pushbuttons to activate
loopbacks.