Each input terminal block includes two pairs of
Compression lugs for various sizes AWG wire are available as accessory items. Nuts with captive washers are included to secure the compression lugs to the studs. The input terminal blocks are located on the rear side of the panel.
The minimum recommended wire size for the input power wiring is #2 AWG copper wire. In selecting wire size, follow local code referring to the ampacity guidelines provided in Appendix A of this manual.
1.11 Output Power Connectors
Depending on the fuse configuration used, the fuse platform will have at least one, and up to four, output power terminal blocks, located on the rear side of the platform. The number present will depend on the fuse type and number of fuse positions. In general, there will be one terminal block per bus for each fuse type present on that bus.
All of the output power terminal blocks are
Copper wire is used for output power wiring. Connections are typically made using
Table 1 gives terminal screw size, maximum terminal width, and accepted wire gauge. In selecting wire size, follow local code referring to the ampacity guidelines provided in Appendix A of this manual.
Table 1. Output Power Terminal Blocks
FUSE | FUSE HOLDER | TERMINAL | MAXIMUM | LUG/AWG | |
RANGE * | |||||
TYPE | MODULE | SCREW SIZE | TERMINAL WIDTH | ||
KLM | All sizes | 0.320 inch (8.128 mm) | #10 to #22 | ||
|
|
|
|
| |
TPA | All sizes | 0.320 inch (8.128 mm) | #10 to #22 | ||
|
|
|
|
| |
GMT | 4- or | 0.325 inch (8.255 mm) | #12 to #22 | ||
|
|
|
|
| |
GMT | 0.260 inch (6.604 mm) | #14 to #22 | |||
|
|
|
|
| |
TPA/GMT | 4 TPA fuses with | 0.320 inch (8.128 mm) | #10 to #22 | ||
| 10 GMT fuses | 0.200 inch (5.080 mm) |
| ||
| #16 to #24 | ||||
|
|
|
|
|
*Output terminal accepts wire sizes in the AWG range given; however, wire size should be determined based on local requirements and practice.
Page 9
© 2006, ADC Telecommunications, Inc.