DETAIL DRAWING OF OUTPUT
TERMINAL BLOCK CONNECTIONS
TIGHTEN TERMINAL SCREWS TO 15
POWER
OF TORQUE
RETURN
TERMINALS
BUS A
GMT FUSED
POWER OUTPUT
TERMINALS
BUS A
KLM/KTK FUSED
POWER OUTPUT
TERMINALS
Figure 17. Output Power Connections
Caution: Connecting the equipment to the wrong circuit may cause damage to the equipment or the fuse platform. Make sure the fuse is the correct type and has the correct current rating as specified by the equipment manufacturer.
Note: The continuous output load of the equipment during normal operation should not exceed 80% of the rated value of the fuse. This allows some room for manufacturing tolerances and voltage fluctuations in the plant power mains.
4.6Connecting Input Power
Input power is supplied to the fuse platform through the single or dual terminal blocks located on the rear of the platform. Each input terminal block consists of two pairs of
The stud pairs are mounted on 0.625 inch centers and accept