1.12 Ground Connectors
Two #10 studs (with nuts) are provided for grounding the fuse platform chassis. The studs are mounted on 0.625 inch (15.875 mm) centers.
Two crimp ring lug terminals for two #10 AWG wires are provided with each fuse platform. The fuse platform may be grounded using only one stud.
1.13 Alarm Contact Operation
The fuse platform contains circuitry that opens and closes a set of alarm contacts when any fuse on the bus fails or when input power to the bus is lost. These contacts may be used to open or close a loop connected to an external alarm system.
The alarm circuitry uses form C alarm relay dry contacts. During normal operation (power applied and all fuses operational), the normally open (NO) contacts remain open and the normally closed (NC) contacts remain closed. When a fuse fails on either bus or power to either is lost, the NO contacts close creating a connection from NO and common and the normally closed (NC) contacts open creating an open circuit between NC and common. The current rating for each set of alarm relay contacts (either two or three sets of contacts are provided) is 110 Vdc/125 Vac maximum voltage, 1.0 Amp maximum switching current.
1.14 Alarm Contact Connectors
The fuse platform is available with either
Warning: Use of one bus only on a dual bus panel will result in false alarms for the unused bus. Power is required on both buses on a dual bus panel for normal operation.
•
•
1.15Fuse Alarm Indicators
A visual fuse alarm indicator (red LED) is provided on the front of each fuse holder module. The fuse alarm indicator lights when any fuse in the corresponding fuse holder fails. The fuse