b.Return wires: Connect to RTN (+) terminals on the A and B input power terminal blocks.
9.Use a torque wrench (with a
10.Route the free end of each input power cable to the office battery source.
TIGHTEN INPUT TERMINAL
NUTS TO 32 POUND FORCE INCHES (3.6 NEWTON METERS) OF TORQUE
Figure 19. Input Power Connections
11.Connect the input power cables to the office battery power source in accordance with applicable local electrical codes and/or National Electrical Codes.
Caution: Do not apply power to the fuse platform until instructed to do so for testing (see Section 6, Operation on page 28).
4.7Installing Protective Covers
Install the rear protective covers over the connectors at the rear of the fuse platform when all the wiring connections are completed. To identify the covers, see Figure 1.
To install the plastic protective cover, thread the four