This appendix provides guidelines for selecting AWG wire size based on the temperature rating of the conductor and the anticipated load. The information contained is from Table
Note: Information for aluminum conductors has been omitted from the table here because copper conductors only are recommended for use with the ADC panel.
Table
SIZE |
| TEMPERATURE RATING OF CONDUCTOR | ||
AWG | 60°C |
| 60°C | 60°C |
KCMIL | (114°F) |
| (114°F) | (114°F) |
|
|
|
| TYPES |
|
|
|
| TBS, SA, |
|
|
|
| SIS, FEP*, |
|
|
|
| FEPB*, MI, |
|
|
|
| RHH*, |
|
|
| TYPES | THHN*, |
|
|
| THHW*, | |
|
|
| FEPW*, | |
|
|
| ||
|
|
| RH*, RHW*, | |
|
|
| THHW*, | |
|
|
| THW*, | XHH, |
| TYPES |
| THWN*, | XHHW* |
|
| XHHW*, | ||
| TW*, |
| ||
| UF* |
| USE*, ZW* | |
18 | .... |
| .... | 14 |
|
|
|
|
|
16 | .... |
| .... | 18 |
|
|
|
|
|
14 | 20* |
| 20* | 25* |
|
|
|
|
|
12 | 25* |
| 25* | 30* |
|
|
|
|
|
10 | 30 |
| 35* | 40* |
|
|
|
|
|
8 | 40 |
| 50 | 55 |
|
|
|
|
|
6 | 55 |
| 65 | 75 |
|
|
|
|
|
4 | 70 |
| 85 | 95 |
|
|
|
|
|
3 | 85 |
| 100 | 110 |
|
|
|
|
|
2 | 95 |
| 115 | 130 |
|
|
|
|
|
1 | 110 |
| 130 | 150 |
|
|
|
|
|
1/0 | 125 |
| 150 | 170 |
|
|
|
|
|
2/0 | 145 |
| 175 | 195 |
|
|
|
|
|
3/0 | 165 |
| 200 | 225 |
|
|
|
|
|
4/0 | 195 |
| 230 | 260 |
|
|
|
|
|
250 | 215 |
| 255 | 290 |
|
|
|
|
|
300 | 240 |
| 285 | 320 |
|
|
|
|
|
350 | 260 |
| 310 | 350 |
|
|
|
|
|
400 | 280 |
| 335 | 380 |
|
|
|
|
|
Page 31
© 2006, ADC Telecommunications, Inc.