20 Document # 50075 Rev B 3/13/95
Secondary Number 24/12 Hour Test Time (49) The test message sent to the
Secondary phone number may be sent every 12 or 24 hours. If the message is to be
sent every 24 hours, leave the factory default entry of zero. If a 12 hour test report
time is needed, enter 1=12 hours.
Start Monitoring Address (50-51) is programmed to indicate the first group of
zones or points to be monitored and reported to the central station. Default is '01'.
Valid entries are '01, 02, 03 and 04'. See Table 3-1.
End Monitoring Address (52-53) is programmed to indicate the last group of zones
or points to be monitored and reported to the central station. Default is '01'. Valid
entries are '01, 02, 03 and 04'. See Table 3-1.
Use the Start and End Monitoring Address programming locations to set the
reporting range of the UNI•COM.
Note: For additional information on the starting and ending addresses,
refer to the host FACP Technical Manual.
Table 3-1: Start and End Monitoring Address
UNI•COM Communication Selection (54)
Leaving address 54 at '0' disables communications to the central station(s). Enter '1'
for zone reporting, receive only. Enter '2' for zone reporting, receive/transmit. Enter
'3' for point reporting, receive only. Enter '4' for point reporting, receive/transmit.
Note: Use receive only selections when using remote annunciators. Be certain to set
one of the annunciators for receive/transmit for EIA-485 communications bus
supervision. Use the receive/transmit entries when annunciators are not installed or
when the UNI•COM receive/transmit function is used to supervise the EIA-485
communication bus. For additional information on the receive/transmit function,
refer to annunciator technical manuals.
Backup Reporting (55) address 55 entry of '0' allows reports to be sent to
Secondary phone number as backup only. Leaving address 55 with the default
setting of '1' permits transmission to either the central station's Primary or Secondary
phone number. The report will be sent to the first available receiver. An entry of '2'
disables reports from being sent to the Secondary phone number.
Touchtone/Rotary Select (56) A '0' programmed in this address by the factory
triggers Touchtone dialing over both phone lines. Select '1' for rotary dialing.
Make Break Ratio (57) Use this address only if you have chosen '1' for address 56.
The make/break ratio is factory set to '0' which is 67/33, but may be changed to '1'
which is a 62/38 ratio.
Address (58) Leave default of 0.
Address (59) Leave default of 0.
Zone Reporting (Factory Default) Point Reporting
START
Addr. 5 0-51 END
Addr. 5 2-53 START
Adtr. 50-51 END
Addr. 5 2-53
Unimode 200 01 01 Unimode 200 01 04
Unimode 4-16 01 01
Unimode II 01 02
1 = Reports status of 56 zones.
2 = Reports status of 120 zones. 1 = Report status of 198 points
1
1
1
1
2