2.3

Technical Data

 

 

Type power

 

 

PROTECT C. 6000 (S)

6000 VA (cos ϕ = 0.7 lag.)

 

 

4200 W

 

PROTECT C. 10000 (S)

10000 VA (cos ϕ = 0.7 lag.)

 

 

7000 W

 

UPS Input (single phase)

1ph~ / N / PE

 

Rated connection voltage

220 / 230 / 240 Vac

 

Voltage tolerance range

176 Vac – 276 Vac ± 3 %

 

without battery operation

 

 

Nominal frequency

50 Hz / 60 Hz

 

 

(automatic detection)

 

Frequency tolerance range

± 4 Hz

 

Curr. consumption (full load)

 

 

PROTECT C. 6000 (S)

31 A

 

PROTECT C. 10000 (S)

50 A

 

Input power factor

λ ≥ 0.98

 

UPS Output (single phase)

 

 

Rated output voltage

220 / 230 / 240 Vac ±1 %

 

 

(configuration via software

 

 

“CompuWatch”)

 

Nominal frequency

50 Hz / 60 Hz ± 0.1 %

 

 

(depending on mains)

 

Voltage waveform

Harmonic distortion

 

 

≤ 2% THD (linear load)

 

 

≤ 6% THD (non-linear load)

 

Current Crest Ratio

3:1

 

Overload behaviour

until 105 % continuous;

 

with existing mains

> 105 % - < 130 % for 10 min.;

 

 

130 % for 1 s

Gapless automatic switch to SBS. Cutoff after 1 minute at persisting overload (backswitch at damping overload = load < 90%).