2.3 | Technical Data |
|
| Type power |
|
| PROTECT C. 6000 (S) | 6000 VA (cos ϕ = 0.7 lag.) |
|
| 4200 W |
| PROTECT C. 10000 (S) | 10000 VA (cos ϕ = 0.7 lag.) |
|
| 7000 W |
| UPS Input (single phase) | 1ph~ / N / PE |
| Rated connection voltage | 220 / 230 / 240 Vac |
| Voltage tolerance range | 176 Vac – 276 Vac ± 3 % |
| without battery operation |
|
| Nominal frequency | 50 Hz / 60 Hz |
|
| (automatic detection) |
| Frequency tolerance range | ± 4 Hz |
| Curr. consumption (full load) |
|
| PROTECT C. 6000 (S) | 31 A |
| PROTECT C. 10000 (S) | 50 A |
| Input power factor | λ ≥ 0.98 |
| UPS Output (single phase) |
|
| Rated output voltage | 220 / 230 / 240 Vac ±1 % |
|
| (configuration via software |
|
| “CompuWatch”) |
| Nominal frequency | 50 Hz / 60 Hz ± 0.1 % |
|
| (depending on mains) |
| Voltage waveform | Harmonic distortion |
|
| ≤ 2% THD (linear load) |
|
| ≤ 6% THD |
| Current Crest Ratio | 3:1 |
| Overload behaviour | until 105 % continuous; |
| with existing mains | > 105 % - < 130 % for 10 min.; |
|
| 130 % for 1 s |
Gapless automatic switch to SBS. Cutoff after 1 minute at persisting overload (backswitch at damping overload = load < 90%).
12