9 Parallel operation

9.1Functionality

PROTECT C. 6000 (S) and C. 10000 (S) was developed for the parallel operation in n+x technology (”n“ stands for the number of necessary appliances for load supply, “x“ stands for the redundancy level). Up to three appliances of the same type can be connected in parallel to raise the output power and/or to receive a higher availability.

The following constellations are possible according to the n+x technology:

1 + 0

Use of 1 unit

max. 6 or 10 kVA

No redundancy

 

 

 

 

1 + 1

Use of 2 units

max. 6 or 10 kVA

Single redundancy

 

 

 

 

1 + 2

Use of 3 units

max. 6 or 10 kVA

Double redundancy

 

 

 

(max. configuration level)

 

 

 

 

2 + 0

Use of 2 units

max. 12 or 20 kVA

No redundancy

 

 

 

 

2 + 1

Use of 3 units

max. 12 or 20 kVA

Single redundancy

 

 

 

(max. configuration level)

 

 

 

 

3 + 0

Use of 3 units

max. 18 or 30 kVA

No redundancy

 

 

 

(max. configuration level)

 

 

 

 