Max. site altitude | up to 1000m at rated power; | ||||||
|
| if the UPS is used above than | |||||
|
| 1000m, decreasing as follows: | |||||
|
|
|
|
|
|
|
|
| Altitude (m) |
| 1000 | 1500 | 2000 | 2500 | 3000 |
|
|
|
|
|
|
|
|
| Power |
| 100% | 95% | 90% | 85% | 80% |
|
|
|
|
|
|
|
|
Colour | Blackline | ||||||
Weight: |
|
|
|
|
|
| |
PROTECT C. 6000 | 90 kg | ||||||
PROTECT C. 6000 S | 35 kg | ||||||
PROTECT C. 6000 BP | 65 kg | ||||||
PROTECT C. 10000 | 93 kg | ||||||
PROTECT C. 10000 S | 38 kg | ||||||
PROTECT C. 10000 BP | 68 kg | ||||||
Dimension W x H x D: |
|
|
|
|
|
| |
PROTECT C. 6000 (S / BP) | 260 mm x 717 mm x 570 mm | ||||||
PROTECT C. 10000 (S / BP) | 260 mm x 717 mm x 570 mm |
The PROTECT C. complies with the product norm EN 50091.
The CE symbol on the unit certifies the compliance to the EG guidelines for 73/23 EEC low voltage and for 89/336 EEC electromagnetic compatibility (EMC), when following the installation instructions in the manual.
For the 73/23 EEC low voltage guidelines
Reference number | EN |
For |
|
Reference number | EN |
| EN |
| EN |
i | Warning: |
This is a UPS product for restricted sales for | |
users only with appropriate knowledge. To avoid | |
| interference, restrictions according installation |
| or additional measures may be required. |
15