10 Maintenance

The PROTECT C. consists of advanced and resistant components. To guarantee a continuous and high availability it is recommended to check the unit (especially the batteries and the fans) in regular intervals (at least every 6 months).

CAUTION:

Before going through the next step disconnect the PROTECT C. from the mains.

10.1Charging the Battery

The battery is automatically charged when the mains is present, irrespective of the operating mode. This is signalled by the "charge" symbol lighting up (see also chapter 4.4.2, page 25).

The complete charging time of the battery after a length discharge period depends, above all, on the number of additional external battery units.

Charging time up to 90% of rated capacity

Only with internal UPS battery

approx.

7 hours

 

 

 

One additional battery unit

approx.

11 hours

 

 

 

Two additional battery units

approx.

16 hours

 

 

 

Three additional battery units

approx.

24 hours

10.2Maintenance

The following maintenance work should be performed:

Task

Interval

Described in

Visual check

6 months

Chapter 10.2.1

Battery/fan check

6 months

Chapters 10.2.2 / 10.2.3

10.2.1Visual Check

When visually checking the unit, check whether:

55