Overload behaviour

up to 105 % continuous;

in battery mode

> 105 % for 10 s

Short circuit behaviour

3 x IN for 300 ms

Battery

Autonomy time (full load with internal battery)

PROTECT C. 6000

8 min.

PROTECT C. 10000

5 min.

Autonomy times with external optional battery expansions (only for PROTECT C. models):

Coupled

Autonomy times (full load)

 

 

battery modules

C.6000

C. 10000

 

 

 

 

1

25 min.

15 min.

 

 

2

45 min.

25 min.

3

60 min.

33 min.

Rated direct voltage (intermediate circuit)

PROTECT C. 6000 (S)

240 Vdc

PROTECT C. 10000 (S)

240 Vdc

Battery charging current

 

PROTECT C. 6000

 

2.0 A

PROTECT C. 6000 S

4.2 A

PROTECT C. 10000

2.0 A

PROTECT C. 10000 S

4.2 A

Recharge time

 

~ 7 h (UPS with internal

to 90% of rated capacity

battery only)

(PROTECT C. – models)

~ 11 h (with 1 battery

 

 

expansion)

~ 16 h (with 2 battery expansions)

~ 24 h (with 3 battery expansions)

13