The greatest possible supply reliability of connected loads is attained by the parallel connection of up to max. three PROTECT 1. UPS systems. The n+x technology thus guarantees maximum reliability through up to double active redundancy on the one hand as well as on the other hand the possibility of increased power with simple redundancy or even only higher UPS power without any redundancy. The relationship between the available output power and the degree of active redundancy can be seen in the following overview:
Parallel system with PROTECT 1.100
Available power | Number of UPS units | ||||
|
|
| |||
1 | 2 | 3 | |||
|
| ||||
|
|
|
|
| |
Active | 0 | 10 kVA | 20 kVA | 30 kVA | |
|
|
|
| ||
redundancy | 1 | 10 kVA | 20 kVA | ||
degree |
|
|
|
| |
2 | 10 kVA | ||||
| |||||
|
|
|
|
| |
Parallel system with PROTECT 1.150 |
|
| |||
|
|
|
| ||
Available power | Number of UPS units | ||||
|
|
| |||
1 | 2 | 3 | |||
|
| ||||
|
|
|
|
| |
Active | 0 | 15 kVA | 30 kVA | 45 kVA | |
|
|
|
| ||
redundancy | 1 | 15 kVA | 30 kVA | ||
degree |
|
|
|
| |
2 | 15 kVA | ||||
| |||||
|
|
|
|
| |
Parallel system with PROTECT 1.200 |
|
| |||
|
|
| |||
Available power | Number of UPS units | ||||
|
|
| |||
1 | 2 | 3 | |||
|
| ||||
|
|
|
|
| |
Active | 0 | 20 kVA | 40 kVA | 60 kVA | |
|
|
|
| ||
redundancy | 1 | 20 kVA | 40 kVA | ||
degree |
|
|
|
| |
2 | 20 kVA | ||||
| |||||
|
|
|
|
| |
|
| 11 |
|
|