The greatest possible supply reliability of connected loads is attained by the parallel connection of up to max. three PROTECT 1. UPS systems. The n+x technology thus guarantees maximum reliability through up to double active redundancy on the one hand as well as on the other hand the possibility of increased power with simple redundancy or even only higher UPS power without any redundancy. The relationship between the available output power and the degree of active redundancy can be seen in the following overview:

Parallel system with PROTECT 1.100

Available power

Number of UPS units

 

 

 

1

2

3

 

 

 

 

 

 

 

Active

0

10 kVA

20 kVA

30 kVA

 

 

 

 

redundancy

1

---

10 kVA

20 kVA

degree

 

 

 

 

2

---

---

10 kVA

 

 

 

 

 

 

Parallel system with PROTECT 1.150

 

 

 

 

 

 

Available power

Number of UPS units

 

 

 

1

2

3

 

 

 

 

 

 

 

Active

0

15 kVA

30 kVA

45 kVA

 

 

 

 

redundancy

1

---

15 kVA

30 kVA

degree

 

 

 

 

2

---

---

15 kVA

 

 

 

 

 

 

Parallel system with PROTECT 1.200

 

 

 

 

 

Available power

Number of UPS units

 

 

 

1

2

3

 

 

 

 

 

 

 

Active

0

20 kVA

40 kVA

60 kVA

 

 

 

 

redundancy

1

---

20 kVA

40 kVA

degree

 

 

 

 

2

---

---

20 kVA

 

 

 

 

 

 

 

 

11