2.3 | Technical Data |
|
|
| Type rating |
|
|
| PROTECT 1.100 | 10000 VA (cos ϕ = 0.7 ind.) | |
|
| 7000 W | |
| PROTECT 1.150 | 15000 VA (cos ϕ = 0.7 ind.) | |
|
| 10500 W | |
| PROTECT 1.200 | 20000 VA (cos ϕ = 0.7 ind.) | |
|
| 14000 W | |
| UPS input | 3ph~ / N / PE |
|
| Rated connection voltage | 400 V/ 230 VAC | |
| Voltage range without | 304 VAC – 478 VAC ± 3 % | |
| battery operation | (rectifier) | |
|
| 176 VAC – 261 VAC VAC ± 3 % | |
|
| (bypass) | |
| Frequency | 50 Hz / 60 Hz | |
|
| (autom. detection) | |
| Frequency tolerance range | ± 4 Hz | |
| Current consumption at full load (max.) | ||
| PROTECT 1.100 | 13 A (3ph~) / 46 A (bypass) | |
| PROTECT 1.150 | 19 A (3ph~) / 68 A (bypass) | |
| PROTECT 1.200 | 25 A (3ph~) / 91 A (bypass) | |
| System disturbance factor | λ ≥ 0.95 | |
| UPS output |
|
|
| Nominal voltage output | 220 / 230 / 240 VAC ± 1% | |
|
| (configuration via | |
|
| “CompuWatch” software ) | |
| Nominal frequency | 50 Hz / 60 Hz ± 0.1% | |
|
| (dependent on mains frequency) | |
| Type of voltage | Sine, distortion | |
|
| ≤ 2% THD (linear load) | |
|
| ≤ 6% THD | |
| Crest factor | 3:1 |
|
|
| 12 |
|