2.3

Technical Data

 

 

 

Type rating

 

 

 

PROTECT 1.100

10000 VA (cos ϕ = 0.7 ind.)

 

 

7000 W

 

PROTECT 1.150

15000 VA (cos ϕ = 0.7 ind.)

 

 

10500 W

 

PROTECT 1.200

20000 VA (cos ϕ = 0.7 ind.)

 

 

14000 W

 

UPS input

3ph~ / N / PE

 

 

Rated connection voltage

400 V/ 230 VAC

 

Voltage range without

304 VAC – 478 VAC ± 3 %

 

battery operation

(rectifier)

 

 

176 VAC – 261 VAC VAC ± 3 %

 

 

(bypass)

 

Frequency

50 Hz / 60 Hz

 

 

(autom. detection)

 

Frequency tolerance range

± 4 Hz

 

Current consumption at full load (max.)

 

PROTECT 1.100

13 A (3ph~) / 46 A (bypass)

 

PROTECT 1.150

19 A (3ph~) / 68 A (bypass)

 

PROTECT 1.200

25 A (3ph~) / 91 A (bypass)

 

System disturbance factor

λ ≥ 0.95

 

UPS output

 

 

 

Nominal voltage output

220 / 230 / 240 VAC ± 1%

 

 

(configuration via

 

 

“CompuWatch” software )

 

Nominal frequency

50 Hz / 60 Hz ± 0.1%

 

 

(dependent on mains frequency)

 

Type of voltage

Sine, distortion

 

 

≤ 2% THD (linear load)

 

 

≤ 6% THD (non-linear load)

 

Crest factor

3:1

 

 

 

12