8.2Faults
PROTECT 1. outputs detailed error messages by means of which you or the service personnel can quickly and accurately localise and interpret any malfunctions that occur. You can find suggestions for action / solutions in the following to correct problems using error descriptions according to chapter 8.1.2:
8.2.1Error Messages
Message / display | Cause | Solution | ||
|
|
| ||
No display, no acoustic | Mains and/or | Check mains connection | ||
signal although system | battery voltage not | again. Check the back- | ||
is connected to the | in tolerance range, | up fuse and the mains | ||
mains current supply. | poss. totally | input miniature circuit | ||
|
|
| discharged battery. | breaker as well. |
|
|
| ||
Mains OK, but UPS | PositionMains input | Switch mains input | ||
does not switch to | use is in “OFF” | miniature circuit breaker | ||
bypass |
|
| position | to “ON” |
|
|
| ||
“Line” LED flashes and | Mains voltage | Check the mains | ||
“Battery” LED lights up | and/or mains | (voltage, frequency) | ||
|
|
| frequency are |
|
|
|
| outside of tolerance |
|
|
|
| ||
“Inverter" LED and | Mains voltage | Try to | ||
"Battery" LED light up. | supply interrupted. | mains voltage (poss. | ||
The acoustic signal | Automatic | fuse triggered in the | ||
sounds every 4 seconds | switchover to | subdistribution?).When | ||
(operating states | battery mode. | the acoustic signal | ||
|
|
|
| sounds every second, |
|
|
|
| the battery is almost |
“Inverter" | LED | and |
| completely discharged. |
"Battery" | LED light up. |
| Carry out a system | |
The acoustic | signal |
| shutdown of your IT | |
sounds | every | second |
| equipment at this point |
(operating state no. 6). |
| in time at the latest. | ||
|
|
| ||
“Fault” LED lights up, | Overload of the | Immediately reduce the | ||
warning signal sounds | UPS System. | capacity utilisation of the | ||
twice per second (error |
| UPS by disconnecting | ||
descriptions no. 12/13). |
| part of your loads. | ||
|
|
|
|
|