automatically. The supply of the inverter through the mains is resumed and the battery charger charges the battery.
The bar graph LED (LED chain above the pictograph) indicates the remaining battery capacity during this operating mode (see chapter 8, p. 48 ff).
6.1.3Bypass OperationHandumgehungspfad |
|
| Energiefluss bei | |
|
| gestörtem WR | ||
| GR | EUE | WR |
|
Netz |
|
|
| |
|
|
|
| |
Netzeingangs- |
|
|
|
|
sicherungs- |
|
|
|
|
automat |
|
|
|
|
| Lade GR |
| Hand- | Gesicherte |
|
| umgehung | Schiene: | |
Schematische |
|
| ||
|
|
|
| |
Darstellung | Batterie |
|
| Verbraucher |
Energiefluss bei gestörtem WR | Power circuit with faulty INV |
Handumgehungspfad | Manual bypass path |
Netz | Mains |
GR | REC |
EUE | SBS |
WR | INV |
Netzeingangssicherungsautomat | Mains input miniature circuit breaker |
Lade GR | Load REC |
Handumgehung | Manual bypass |
Gesicherte Schiene | Secured busbar |
Schematische Darstellung | Schematic diagram |
Batterie | Battery |
Verbraucher | Load |
If the inverter is overloaded or if overtemperature is detected, e.g. also if an inverter defect is detected, voltage is supplied to the load without interruption via the static bypass switch (SBS) that switches on automatically. This is signalled by the Bypass LED.
42