Agilent Technologies Serials 3004A-05881 to 05885 3023A-06181 and above Agilent 6033A Ampacity

Models: Serials 2934A-01825 to 01829 3023A-01925 Serials 2934A-01821 to 01825 3026A-01921 and above Agilent 6032A

1 129
Download 129 pages 812 b
Page 37
Image 37
Table 3-3. Stranded Copper Wire Ampacity

If multiple loads are connected to one supply, each load should be connected to the supply’s output terminals using separate pairs of connecting wires. This minimizes mutual coupling effects and takes full advantage of the supply’s low output impedance. Each pair of connecting wires should be as short as possible and twisted or shielded to reduce noise pickup and radiation.

If load considerations require the use of output distribution terminals that are located remotely from the supply, then the power supply output terminals should be connected to the remote distribution terminals by a pair of twisted or shielded wires and each load should be separately connected to the remote distribution terminals. Remote voltage sensing is required under these circumstances (page 39). Sense either at the remote distribution terminals, or (if one load is more sensitive than the others) directly at the most critical load.

Table 3-3. Stranded Copper Wire Ampacity

Wire Size

AWG

Cross Section Area in mm2

Ampacity

NOTES:

22

20

18

16

4

12

10

6

8

6

4

2

0

0,75

1

1.5

2.5

4

10

5.0

8.33

10

15.4

13.5

19.4

16

31.2

25

40

32

55

40

75

63

100

135

180

245

1.Ratings for AWG-sized wires are derived from MIL-W-5088B. Ratings for metric-sized wires are derived from IEC Publication 335-1.

2.Ampacity of aluminum wire is approximately 84% of that listed for copper wire.

3.When two or more wires are bundled

together, ampacity for each wire

must be reduced to the following percentages:

2 conductors 94%

3 conductors 89%

4 conductors 83%

5 conductors 76%

4.Maximum temperatures: Ambient, 50°C; Conductor, 105°C

Either positive or negative voltages can be obtained from the supply by grounding one of the output terminals. It is best to avoid grounding the output at any point other than the power supply output terminals to avoid noise problems caused by common-mode current flowing through the load leads to ground. Always use two wires to connect the load to the supply regardless of where or how the system is grounded. Never ground the system at more than one point. The maximum potential (including output voltage) that either output terminal is from ground must not exceed that specified on the output label on the rear chassis.

The PARD specifications in Table 1-1 apply at the power supply output terminals. However, noise spikes induced in the load leads at or near the load may affect the load although the spikes are inductively isolated from the power supply. To minimize voltage spikes at the load, connect a bypass capacitor as shown in Figure 3-5. With this setup, peak-to-peak noise at the load can actually be reduced to a level well below the value specified at the power supply output terminals.

Operating Instructions 37

Page 37
Image 37
Agilent Technologies Serials 3004A-05881 to 05885 3023A-06181 and above Agilent 6033A Cross Section Area in mm2, Ampacity