WIRE THE INDOOR UNIT

WIRE THE INDOOR UNIT

REASSEMBLE

1.

Strip the cables back 1/4 inch.

1.

Connect the display connector to the display panel printed

2.

Remove the unit's front panel by lifting the lower part and

 

circuit board.

 

 

 

pulling it gently outward and upward. See Fig. 6.

2.

Put the control box cover and grille frame back on using the

3.

Remove the two screws from the control box cover and take

 

appropriate screws (Steps 3 and 4 of Wire the Indoor Unit

 

section). Put the grille insert back on.

 

off the cover. See Fig. 7. Save the screws to reassemble.

 

 

 

 

NOTE: In general wiring the indoor unit does not require the removal of the grille frame but in case of need do as follow:

4.Remove the two screws from the air discharge opening. Save the screws to reassemble. See Fig. 7A.

Pull downwards and outwardston the bottom of the grille

and gently raise the frame of the top of the unit.

• Once all covers are off, mount the unit onto the wall mounting bracket. See Fig. 8 .

NOTE: Leave covers off until after the Making Drainage Con-

Fig. 6 — Remove Grille Insert

nections section.

 

• Route the interconnecting unit's electric cable and the

 

outdoor sensor cable towards the lower right hand corner of

AUTO/OFF

 

FILTER RESET

the indoor unit.

 

• Make sure that the wires are connected in accordance with

SERVICE LED

 

the wiring diagram on the inside of the unit front cover or

 

within this instruction manual.

 

• Secure the control cables to the strain relief.

• For heat pump systems only, connect the outdoor sensor

Fig. 7 — Remove Control Cover

TH3 to its mating black terminal. See Fig. 9.

CAUTION

 

Make sure that all wires and screws are firmly fastened. Loose

 

wires or connections can cause damage and present a fire

Fig. 7A - Remove the screws from the air

hazard.

MAKE DRAINAGE CONNECTIONS

discharge opening.

Mount the indoor unit on the mounting bracket

1. Connect the unattached end of the drainage tube to the

 

drainage hose outlet.

1

 

2. Seal the drainage connection to prevent leakage.

3. Make sure there are no kinks, "U" bends or flattened sections in the tube.

4. Check that the drainage functions properly. Fill the pan below the unit's coil with water and observe that it freely drains out.

5. Make sure the drainage hose is at the bottom side of the wall

2

through-hole (see Fig. 5).

 

 

Gently push with the arrow direction

 

Fig. 8 — Indoor Unit Mounting

 

Standard Dip Switches

 

status from the factory

HEAT PUMP

 

Model-2 X12 DIP Switches location

Inter unit

(on the Control Box side)

terminal block

 

HEAT PUMP

30VDC

 

Models-2 X 09 DIP Switches location

Display

(on the Control Box side)

 

Connection

COOLING ONLY

 

Model-2 X12 DIP Switches location

 

(on the Control Box side)

 

COOLING ONLY

TH1

TH2

Models-2 X09 DIP Switches location

(on the Control Box side)

TH3

 

(Heat Pump Only)

 

Inter unit cable clamp

 

Fig. 9 — Outdoor Sensor Connection

 

5

Page 5
Image 5