Agilent Technologies Serials 3004A-05092 to 05096 3024A-05272 and above Agilent 6035A manual

Models: Serials 2934A-01825 to 01829 3023A-01925 Serials 2934A-01821 to 01825 3026A-01921 and above Agilent 6032A

1 129
Download 129 pages 812 b
Page 70
Image 70
Fault Input (FLT) and Remote Inhibit (INH) Connections

It is not recommended that Agilent 6035A supplies be connected in series. if you do so, the common connection between the two supplies must be connected to earth ground (see Figure 3-15).

Add the voltage settings of each power supply together to determine the total output voltage. Set the current limits for each power supply to the maximum that the load can handle without damage.

Figure 3-15. Series OperationWhen two supplies are operated in series, they should be programmed to the same voltage to prevent possible damage to the lower voltage supply during short circuit conditions. Contact the factory if this is not possible.

Fault Input (FLT) and Remote Inhibit (INH) Connections

The connections for FLT and INH are made through a connector which is located on the rear of the power supply just below the GP-IB address/PON selection switches. The connector is supplied with its mating plug which provides a convenient way to access the FLT and INH circuitry (see Figure 3-16). To remove the plug grip it firmly, then pull it straight out of the connector. With a small screwdriver, loosen the terminal screws on the plug; connect the external FLT and/or INH circuitry, then install the plug back into the connector. Note that in order to prevent radio frequency interference (RFI), shielded or twisted pair wiring should be used for the FLT and INH connections. To prevent ground loops (if shielded wire is used) connect only one end of the shield to chassis ground. Several examples follow.

Figure 3-15. Series Operation

In Figure 3-17 shows a way to protect a load if the controller is halted during a debugging session. An externally, normally open switch (S1) is mounted on a hinged protection hood which covers the device under test. The terminals of the switch are connected to the INH input line. When the hood is lifted, the switch closes and the following simultaneous actions are taken by the power supply:

1.The power supply is disabled (as it is when an OUT OFF or OUT 0 is issued).

2.The RI bit in the status and astatus registers is set true (1).

3.The FLT line goes true (1) (provided the RI bit in the unmasked register has been set true (1)).

4.If the RI bit in the unmasked register has been set true (1) then the RI bit in the fault register will be set true (1) and the FAU bit in the serial poll register will be set true (1).

70Operating Instructions

Page 70
Image 70
Agilent Technologies Serials 3004A-05092 to 05096 3024A-05272 and above Agilent 6035A, Agilent 6031A 15. Series Operation