User Menu: Set Alarm Parameters U200 series

iCOM Control Training and Service Manual

User Menu: Set Alarm Parameters U200 series

 

Menu Line

 

 

Parameter

 

 

Default

 

 

Range

 

 

 

 

 

 

 

 

 

 

U201

 

Password

-

 

-

 

 

 

 

 

 

 

 

 

 

U202

 

 

Return Sensor Alarms

 

 

Enabled

 

 

Enabled or Disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U203

 

High Return Temperature

 

80ºF

 

33 - 210ºF

 

 

 

 

 

 

 

 

 

U204

 

 

Low Return Temperature

 

 

60ºF

 

 

33 - 210ºF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U205

 

High Return Humidity

60%

 

 

1 – 99%

 

 

 

 

 

 

 

 

 

U206

 

 

Low Return Humidity

 

 

40%

 

 

1 – 99%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U207

 

Sensor A Alarms

 

Disabled

 

Disabled or Enabled

 

 

 

 

 

 

 

 

 

U208

 

 

High Temperature Sensor A

 

 

90ºF

 

 

33 - 210ºF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U209

 

Low Temperature Sensor A

 

55ºF

 

33 - 210ºF

 

 

 

 

 

 

 

 

 

U210

 

 

High Humidity Sensor A

 

 

70%

 

 

1 - 99%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U211

 

Low Humidity Sensor A

30%

 

1 - 99%

 

 

 

 

 

 

 

 

 

 

 

 

 

User Menu: Sensor Data U300 series: Page 1 of 2

 

Menu Line

 

 

Parameter

 

 

Range

 

 

 

 

 

 

 

 

U301

 

Actual Temperature Setpoint

 

41 – 104ºF

 

 

 

 

 

 

 

U302

 

 

Actual Humidity Setpoint

 

 

20 – 80%

 

 

 

 

 

 

 

 

 

 

 

U303

 

Optional Sensor A Temperature

 

32 - 122ºF

 

 

 

 

 

 

 

U304

 

 

Optional Sensor A Humidity

 

 

20 – 80%

 

 

 

 

 

 

 

 

 

 

 

U305

 

Optional Sensor B Temperature

 

32 - 122ºF

 

 

 

 

 

 

 

U306

 

 

Optional Sensor B Humidity

 

 

20 – 80%

 

 

 

 

 

 

 

 

 

 

 

U307

 

Optional Sensor C Temperature

 

32 - 122ºF

 

 

 

 

 

 

 

U308

 

 

Optional Sensor C Humidity

 

 

20 – 80%

 

 

 

 

 

 

 

 

 

 

 

U309

 

Freecooling Fluid Temperature

 

4 - 113ºF

 

 

 

 

 

 

 

U310

 

 

DigiScroll 1 Temperature

 

 

84 - 313ºF

 

 

 

 

 

 

 

 

 

 

 

U311

 

DigiScroll 2 Temperature

 

84 - 313ºF

 

 

 

 

 

 

 

 

 

U312

 

 

Freecooling Status

 

 

Off, Start, On

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

63