Events Notifications Parameters (continued)

iCOM Controls Training and Service Manual

Events Notifications Parameters (continued)

ID

Type

Description (Large Display)

Description (Small Display)

111

Warning

EL.HEAT 1 HOURS

EL.HEAT 1 HOURS EXC.

EXCEEDED

 

 

 

112

Warning

EL.HEAT 2 HOURS

EL.HEAT 2 HOURS EXC.

EXCEEDED

 

 

 

113

Warning

EL.HEAT 3 HOURS

EL.HEAT 3 HOURS EXC.

EXCEEDED

 

 

 

Event ID number, Description and Function

ID

Description

Event explanation

Default

Shut

Rotat

restart if

 

 

 

Type

down

e

duty unit

 

 

 

 

single

stand

fails also

 

 

 

 

unit

by

 

 

000

GENERAL

Warning or Alarm was

Reset

-

-

-

 

 

 

ALARM

acknowledged or reset

 

 

 

 

 

 

001

COMP 1 HIGH

Compressor 1 stopped

Alarm

no

yes

yes

 

 

 

PRESSURE

because of high pressure

 

 

 

(broken co

 

 

 

 

 

 

 

 

will remain

 

 

 

 

 

 

 

 

off)

 

 

002

COMP 1 LOW

Compressor 1 stopped

Alarm

no

yes

yes

 

 

 

PRESSURE

because of low pressure

 

 

 

(broken co

 

 

 

 

 

 

 

 

will remain

 

 

 

 

 

 

 

 

off)

 

 

003

HIGH CW

chilled water temperature

Warning

no

no

-

 

 

 

TEMP

too high (input from

 

 

 

 

 

 

 

 

thermostat)

 

 

 

 

 

 

004

LOSS OF CW

chilled water flow too low

Warning

no

no

-

 

 

 

FLOW

(input from flow switch)

 

 

 

 

 

 

005

EL HEAT HIGH

electric heaters stopped

Warning

no

no

-

 

 

 

TEMP

because of too high

 

 

 

 

 

 

 

 

temperature on the

 

 

 

 

 

 

 

 

safety thermostat

 

 

 

 

 

 

006

MAIN FAN

fan motor protection has

Alarm

yes, if

yes

yes, only if

 

 

 

OVERLOAD

stopped the fan due to

 

set to

 

set to

 

 

 

 

overload.

 

shut

 

"disable"

 

 

 

 

this event can be set to

 

down

 

 

 

 

 

 

switch off the unit or to

 

 

 

 

 

 

 

 

disable hum and electric

 

 

 

 

 

 

 

 

heat.

 

 

 

 

 

92

Page 93
Image 93
Liebert TM-10098 Events Notifications Parameters continued, Event ID number, Description and Function, Type, Default, Shut