Liebert TM-10098 iCOM Controls Training and Service Manual, Small Display Jumper Settings, Type

Models: TM-10098

1 170
Download 170 pages 16.13 Kb
Page 107
Image 107
Small Display Jumper Settings

iCOM Controls Training and Service Manual

Small Display Jumper Settings

 

 

 

 

 

Jumper

 

 

 

 

Type

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P4

 

Manual Contrast

 

* Shunt on Pins 2 & 3

 

 

 

 

 

 

 

 

 

 

(Rev. 2 only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P78

 

 

CAN Termination

 

 

* Shunt on Pins 2 & 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P80

 

BDM Header

 

 

 

* open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P82

 

 

Watchdog

 

 

* Shunt on Pins 1 & 2

 

 

 

 

 

 

 

 

 

 

 

 

(Rev. 2 Only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Default Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature/ Humidity Board DIP Switch #1 Settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Position

 

 

Type

 

 

 

Setting

 

 

 

 

Notes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

CAN Address

 

Off

 

 

 

 

 

On (if Sensor A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

CAN Address

 

 

Off

 

 

 

 

 

On (if Sensor B)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

CAN Address

 

Off

 

 

 

 

 

On (if Sensor C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

CAN Address

 

 

Off

 

 

 

 

 

open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

CAN Address

 

On (Normal &

 

 

 

 

Off (Analog Mode)

 

 

 

 

 

 

Constant Operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

CAN Address

 

 

Off (Normal Operation)

 

 

On (Analog Mode &

 

 

 

 

 

 

 

 

 

 

 

Constant Operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

CAN Baud

 

Off

 

 

 

 

 

open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

CAN Baud

 

 

Off

 

 

 

 

 

open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature/ Humidity Board Jumper Settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Jumper

 

 

 

 

Type

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2

 

BDM Header

 

 

* open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P3

 

 

CAN Termination

 

 

* Shunt on Pins 2 & 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P4

 

Programming

 

 

* open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Default Setting

106

Page 107
Image 107
Liebert TM-10098 iCOM Controls Training and Service Manual, Small Display Jumper Settings, Type, Default Setting, Position