iCOM Control Training and Service Manual

Note: in the above example that the control band begins at the 50% humidity set point and has a length of 4%, which is ½ of the programmed humidity proportional band value.

As the return air humidity increases, dehumidification operation is activated at 54%RH or 100% of the dehumidification control band. When the return air humidity starts to decrease, dehumidification operation is deactivated at 52%RH or 50% of the humidity proportional control band.

1 Stage Compressorized Dehumidification – With Dead Band

Humidity Set Point - (1/2 Dead Band +1/2 Proportional Band)

Humid Set Point: 50%

 

 

 

 

Proportional Band: 8%

 

 

 

 

Dead Band: 2%

 

 

 

Dehumidification On

 

 

 

 

50

51

52

53

54

55

DB

 

 

 

 

 

 

 

Dehumidification Off

 

 

 

 

 

Increasing Humidity

Note: in the above example that the control band begins at the 50% humidity set point and has a length of 5%, which is ½ of the programmed dead band value plus ½ of the programmed proportional band value.

As the return air humidity increases, dehumidification operation is activated at 55% RH or ½ of the dead band value plus 100% of the dehumidification control band. When the return air humidity starts to decrease, dehumidification operation is deactivated at 53%RH or ½ of the dead band value plus 50% of the humidity proportional control band.

2-Stage Dehumidification, Compressorized Direct Expansion (DX) Systems

The basic dehumidification control band is established at the humidity set point with the length equal to ½ of the programmed humidity proportional band value. When 2 stage dehumidification is selected, the controller works as follows.