Liebert TM-10098 service manual DS Systems, iCOM Control Training and Service Manual, P3: Not Used

Models: TM-10098

1 170
Download 170 pages 16.13 Kb
Page 108
Image 108
DS Systems:

iCOM Control Training and Service Manual

DS Systems:

P3: Not Used

P4: 24 VAC Power

 

 

 

P4-1:

Fuse 1 (24 VAC)

P4-3:

Fuse 3 (24 VAC)

P4-2:

Fuse 2 (24 VAC)

P4-4:

Fuse 4 (24 VAC)

P7: Fluid Sensor

 

 

 

P7-1:

Aquastat Sensor

 

 

 

P7-2:

Aquastat Sensor

 

 

 

P8: 24 VAC Alarm Inputs

 

 

 

P8-1:

24 VAC (RAD1/ TS 50)

P8-5:

24 VAC (HWA)

P8-2:

24 VAC (RAD2/ TS 51)

P8-6: 24 VAC Out (TS 24)

P8-3:

24 VAC (RAD3/ TS 55)

P8-7: 24 VAC Out (HWA)

P8-4:

24 VAC (RAD4/ TS 56)

P8-8:

no connection

P11: Low Pressure Switch Circuits

 

P11-1: DCV Signal to LPT1

 

 

 

P11-2: Cold Start Bypass 1 Signal

 

P11-3: LPT1 Input to MP

 

 

 

P11-4:

 

 

 

 

P11-5: DCV Signal to LPT2

 

 

 

P11-6: Cold Start Bypass 1 Signal

 

P11-7: LPT2 Input to MP

 

 

 

P11-8:

 

 

 

 

P12: Analog Sensor Inputs

 

 

 

P12-1:

T+ Analog 1 (TS 41)

P12-5: T+ Analog 3 (TS 45)

P12-2:

T- Analog 1 (TS 42)

 

P12-6: T- Analog 3 (TS 46)

P12-3:

T+ Analog 2 (TS 43)

P12-7: T+ Analog 4 (TS 47)

P12-4:

T- Analog 2 (TS 44)

 

P12-8:

T- Analog 4 (TS 48)

P13: DCV Thermistor Signals

P13-1: DCV Signal to Digital Scroll Thermistor 1

P13-2: DCV Signal from Digital Scroll Thermistor 1

P13-3: DCV Signal to Digital Scroll Thermistor 2

P13-4: DCV Signal from Digital Scroll Thermistor 2

P13-5: DCV Signal to Customer Thermistor

P13-6: DCV Signal from Customer Thermistor

107

Page 108
Image 108
Liebert TM-10098 DS Systems, iCOM Control Training and Service Manual, P3: Not Used, P4 24 VAC Power, P7: Fluid Sensor