DIG SCROLL2

iCOM Control Training and Service Manual

098

DIG SCROLL2

Digital Scroll compressor

Alarm

no

yes

yes

 

HIGH TEMP

#1 shut off because of

 

 

 

(broken co

 

 

high temperature (sensor

 

 

 

will remain

 

 

is inside the

 

 

 

off)

 

 

compressor).

 

 

 

 

103

SHORT CYCLE

compressors are

Message

-

no

-

 

 

requested from control to

 

 

 

 

 

 

start too often - control is

 

 

 

 

 

 

unstable.

 

 

 

 

104

SMOKE

customer input is active.

Alarm

no

yes

yes (if not

 

DETECTED

 

 

 

 

disabled

 

 

 

 

 

 

externally)

 

 

 

 

 

 

 

105

WATER

customer input is active.

Alarm

no

yes

yes (if not

 

UNDER

 

 

 

 

disabled

 

FLOOR

 

 

 

 

externally)

106

COND PUMP-

customer input is active.

Alarm

no

yes

yes (if not

 

HIGH WATER

 

 

 

 

disabled

 

 

 

 

 

 

externally)

107

LOSS OF

customer input is active.

Alarm

no

yes

yes (if not

 

FLOW

 

 

 

 

disabled

 

 

 

 

 

 

externally)

108

STBY GLYCOL

customer input is active.

Alarm

no

yes

yes (if not

 

PUMP ON

 

 

 

 

disabled

 

 

 

 

 

 

externally)

109

STANDBY

customer input is active.

Alarm

no

yes

yes (if not

 

UNIT ON

 

 

 

 

disabled

 

 

 

 

 

 

externally)

110

HW/HG HRS

actual working hours of

Warning

no

no

-

 

EXCEEDED

hot water heat / hot gas

 

 

 

 

 

 

reheat are higher than

 

 

 

 

 

 

the threshold set.

 

 

 

 

111

EL HEAT1 HRS

actual working hours of

Warning

no

no

-

 

EXCEEDED

electrical heater stage 1

 

 

 

 

 

 

are higher than the

 

 

 

 

 

 

threshold set.

 

 

 

 

112

EL HEAT2 HRS

actual working hours of

Warning

no

no

-

 

EXCEEDED

electrical heater stage 2

 

 

 

 

 

 

are higher than the

 

 

 

 

 

 

threshold set.

 

 

 

 

113

EL HEAT3 HRS

actual working hours of

Warning

no

no

-

 

EXCEEDED

electrical heater stage 3

 

 

 

 

 

 

are higher than the

 

 

 

 

 

 

threshold set.

 

 

 

 