Autoflush Control Flow Chart

iCOM Control Training and Service Manual

If the off time is less than 15 hours (or user programmed value) the pre-fill program is bypassed and the infrared lamps and water valve are activated at the same time to fill the pan to the proper water level and initiate humidification.

During normal infrared humidification operation the water makeup valve is periodically closed (no pan fill) and opened (pan fill) based on a timing sequence to allow for the evaporation of water from the pan (see flow chart below).

With the humidifier water flush rate set at the factory default value of 150% the water makeup valve will open for 7 minutes of fill time with an off time of 45 seconds between fill cycles for a small pan. For a large pan water makeup valve will open for 10 minutes of fill time with an off time of 80 seconds between fill cycles. The user can modify the percentage from 110% to a maximum of 500% in 1% increments.

Call for Humidification

Autoflush Control Flow Chart

 

 

 

 

 

 

 

On in last

 

NO

HMV Pre-fill

 

15 Hours?

 

 

30 sec – small pan

 

 

 

 

60 sec – large pan

 

 

YES

 

 

 

 

HMV and Lamps on 4 min – small pan 7 min – large pan

Humidification Lamps only

8 min – small pan

10 min – large pan

Refill

110% to 500%

Notes:

1.IFL: Infra-red Large and IFS: Infra-red Small

2.Last 15 Hours is programmable from 1-120hours.

3.Pre-fill time is programmable from 1-120 seconds on Large or Small pans

4.Normal Fill is programmable from 1-120 seconds

5.Refill is programmable in 1% increments