Glycool at 50% Capacity – No Dead Band

iCOM Controls Training and Service Manual

Glycool at 50% Capacity – No Dead Band

Temp Set Point + (1/2 Proportional Band + 1/2 Proportional Band)

Temp Set Point: 70°

 

 

 

 

 

 

 

Proportional Band: 8°

 

 

 

 

 

 

 

 

 

100%

Cool 1 On

Cool 2 On

 

 

Valve

Open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Closed

 

 

 

 

 

 

 

 

70

71

72

73

74

75

76

77

78

79

 

Band 1

 

Band 2 Compressors

 

 

 

 

 

Glycool

 

 

 

 

 

 

 

 

 

Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Increasing Temperature

Dual Source Cooling

When supplied with the Dual Cooling option, the basic unit is supplied with an additional coil, piping, valve and a Glycol Fluid Sensor (AQ), which is mounted to the unit supply fluid line and serves as control interface in determining the system operation. Selection of the chilled water or compressorized operation is controlled by microprocessor using this aquastat to sense the water temperature.

The Dual Source Cooling program establishes two distinct control bands for cooling control operation in the same method as Glycool. The first band controls the operation of the chilled water valve and the second controls the operation of the compressors, either 2-stage or 4-stage.

The microprocessor checks the return air temperature and the entering chilled water fluid temperature to determine a cooling capacity. The chilled water cooling capacity is considered to be 100% if the entering Chilled Water fluid temperature is 8°F lower than the return air temperature.

When the microprocessor decides that the return chilled water temperature is cold enough the first cooling band is the modulating valve control method, and the second band, added to the first band, is for the compressors as in the normal